3.2.1.10 Number of Poles
This screen enables to set No. of poles of a Generator of which RPM is to be measured and to
which the instrument is connected to monitor its parameters.
INVALID VALUE
NUMBER OF POLES
The valid range of number of poles is from
2 to 40
.
If an odd value or a value outside the range is entered, It will display
“INVALID VALUE” followed by the correct range of parameter.
Touch on “ key” will conrm the setting and will return to
previous menu. Touching the “ key” will keep the old selected
setting.
3.2.1.9 Low Current noise cutoff
This screen allows the user to set Low noise current cutoff in mA.
Two options, 0 MILLI-AMPERE & 30 MILLI-AMPERE are displayed on
screen. Touching radio button in front of particular option will select
that option.
Touch on “ key” will conrm the setting.
Touching the “ key” will keep the old selected setting and will
return to previous menu.
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LOW CURRENT NOISE CUTOFF
0 MILLI-AMPERE
30 MILLI-AMPERE
OK
BACK
BACK
OK
OK
BACK
OK
OK
depending as per the user’s requirement.
This setting is applicable for all types of energy.
Three options: WATT, KILO-WATT & MEGA-WATT are displayed on
screen. Touching radio button in front of particular option will select
that option.
Touch on “ key” will conrm the setting.
Touching the “ key” will keep the old selected setting and will
return to previous menu.
3.2.1.11 Energy Resolution
This screen enable user to set energy in terms of Wh / kWh / MWh on Rs485 Output
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
ENERGY ON RS485
WATT (W)
KILO-WATT (KW)
MEGA-WATT (MW)
OK
BACK
Note : Default value is set to ‘WATT’ i.e. Energy on Modbus will be in terms of
Wh/VArh/VAh respectively.
19