check flow
through the
installation
16.1.2
Blocage / Block 11
see the installation instructions for the hydraulic
connections to the boiler
(3-Way-Thermostatic valve, Plumbing Kit
installed?)
maximum average
T of supply and return
sensor for central heating is repeatedly
exceeded. Operation is normally possible
for the hot water supply during the block.
The pump continues to operate at minimum
capacity during the block.
possible causes: (radiator) shut-off valves
closed or blocked water filter
check pump height.
check minimum and maximum Temperature
difference in Parameter Step 46 + 47.
activeted room sensor (RS101) in non leading
room (closed thermostatic radiator valves?)
vérifiez le débit
dans toute
l’installation
consultez les instructions d’installation pour
les raccordements hydrauliques à la chaudière
(vanne thermostatique 3 voies, kit de plomberie
installés ?)
Le
T maximum moyen du capteur
d’alimentation et de retour du le chauffage
central a été dépassé plusieurs fois. Pendant
le blocage, le fonctionnement normal de
l’alimentation en eau chaude est possible. La
pompe continue à fonctionner à sa capacité
minimale pendant le blocage
causes possibles : (radiateur) vannes d’arrêt
fermées ou filtre à eau bloqué
vérifiez la hauteur de la pompe.
vérifiez la différence de température minimale
et maximale dans Paramètre Etape 46 + 47.
capteur d’ambiance activé (RS101) dans une
pièce non centrale (vannes thermostatiques
de radiateur fermées ?)
Summary of Contents for Q130SN
Page 18: ...Installation Servicing Instructions Rinnai Q Series 18 Boiler basic piping fig 6 ...
Page 44: ...Installation Servicing Instructions Rinnai Q Series 44 electrical ladder diagram figure 22a ...
Page 99: ...Installation Servicing Instructions Rinnai Q Series 99 ...
Page 119: ...Installation Servicing Instructions Rinnai Q Series 119 ...
Page 120: ......