OUTLET AIR DUCT
INLET AIR DUCT
Gas Vent / Boiler Exhaust
BOILER
12in. MAX
12in. MAX
PERMANENT
OPENINGS
BOILER
10"
(250mm)
12"
(300mm)
Louvers and grills figure 19
Confined Space:
(Small Room, Closet, Alcove, Utility Room, Etc.)
A confined space is defined in the NFPA #54 as "a space whose volume is less than
50 cubic feet per 1000 Btu/hr (4.8 m3 per kW per hour) of the aggregate input rating
of all appliances installed in that space." A confined space must have two combustion
air openings. Size the combustion air openings based on the BTU input for all gas
utilization equipment in the space and the method by which combustion air is supplied:
Using indoor air for combustion
Using outdoor air for combustion
Louvers and Grills
When sizing the permanent opening as illustrated in figure 18, consideration must be
taken for the design of the louvers or grills to maintain the required free area required
for all gas utilizing equipment in the space. If the free area of the louver or grill design
is not available, assume wood louvers will have 25% free area and metal louvers or
grills will have 75% free area. Under no circumstance should the louver, grill or screen
have openings smaller than ¼”.
Example:
Wood: 10 in x 12 in x 0.25 = 30 in2
Metal: 10 in x 12 in x 0.75 = 90 in2
Location
To maintain proper circulation of combustion air two permanent openings (one upper,
one lower) must be positioned in confined spaces. The upper shall be within 12 inches
of the confined space and the lower opening shall be within 12 inches of the bottom
of the confined space. Openings must be positioned as to never be obstructed.
Combustion air provided to the appliance should not be taken from any area of the
structure that may produce a negative pressure (i.e. exhaust fans, powered ventilation
fans).
Summary of Contents for Q130SN
Page 18: ...Installation Servicing Instructions Rinnai Q Series 18 Boiler basic piping fig 6 ...
Page 44: ...Installation Servicing Instructions Rinnai Q Series 44 electrical ladder diagram figure 22a ...
Page 99: ...Installation Servicing Instructions Rinnai Q Series 99 ...
Page 119: ...Installation Servicing Instructions Rinnai Q Series 119 ...
Page 120: ......