7. Maintenance
7-10 Making changes in Environmental setting 2
118 / 191
7-10-7 Alarm type setting (ALM TYPE)
Set the alarm type for each sensor.
When an oxygen deficiency alarm model sensor is fitted, any of H-HH type, L-LL type, or L-H type can be
set.
The default setting is H-HH type.
NOTE
Several alarm type settings are possible for oxygen deficiency specification sensors. For other
sensors, it will be H-HH type.
1 In maintenance mode, press the
▲
key or
▼
key to
select [2-10 SETTING2], then press the TEST/SET key.
2 Press
the
▲
key or
▼
key to select [SET- 7 ALM TYPE],
then press the TEST/SET key.
3 Press
the
▲
key or
▼
key to select the sensor.
Press the
▲
key or
▼
key repeatedly to cycle through the
following settings: [A1]
⇔
[A2]
⇔
[B1]
⇔
[B2].
The setting value for the selected sensor blinks.
4 Press the TEST/SET key to confirm the sensor.