7. Maintenance
7-10 Making changes in Environmental setting 2
114 / 191
7-10-5 Settings for external output during alarm tests (TEST4-20)
Set the external output during alarm tests ON or OFF.
Set to ON to use external output (4 - 20 mA) during alarm tests.
When set to OFF, the output from immediately before the alarm test is maintained.
1 In maintenance mode, press the
▲
key or
▼
key to
select [2-10 SETTING2], then press the TEST/SET key.
2 Press
the
▲
key or
▼
key to select [SET- 5 TEST4-20],
then press the TEST/SET key.
3 Press
the
▲
key or
▼
key to select [ON] or [OFF],
then press the TEST/SET key.
The display reverts to the [SET- 5 TEST4-20] display.
4 Press the MODE key.
The display reverts to the [2-10 SETTING2] display.
NOTE
Press the MODE key in step 3 to cancel the settings and return to the [SET- 5 TEST4-20] display.
4-20mA
EA