7. Maintenance
7-9 Making changes in Environmental setting 1
101 / 191
7-9-2 Alarm setpoints (ALM P)
Set the gas alarm setpoints (first alarm setpoint, second alarm setpoint) for each sensor.
1 In maintenance mode, press the
▲
key or
▼
key to
select [2- 9 SETTING1], then press the TEST/SET key.
2 Press
the
▲
key or
▼
key to select [SET- 1 ALM P], then
press the TEST/SET key.
3 Press
the
▲
key or
▼
key to select the sensor.
Press the
▲
key or
▼
key repeatedly to cycle through the
following settings: [A1]
⇔
[A2]
⇔
[B1]
⇔
[B2].
The setting value for the selected sensor blinks.
4 Press the TEST/SET key to confirm the sensor.
5 Press
the
▲
key or
▼
key to set the alarm value for the
first alarm setpoint, then press the TEST/SET key.
<First alarm setpoint setting>