7. Maintenance
7-9 Making changes in Environmental setting 1
100 / 191
3 Press
the
▲
key or
▼
key to select the sensor.
Press the
▲
key or
▼
key repeatedly to cycle through
the following settings: [A1]
⇔
[A2]
⇔
[B1]
⇔
[B2].
The setting value for the selected sensor blinks.
4 Press the TEST/SET key to confirm the sensor.
5 Press
the
▲
key or
▼
key to select [OFF] or [ON],
then press the TEST/SET key.
The display reverts to the display in step 3.
To continue making settings for other sensors, repeat steps 3 to 5.
6 Press the MODE key after making the settings.
The display reverts to the [SET- 0 INHIBIT] display.
7 Press the MODE key.
The display reverts to the [2- 9 SETTING1] display.
NOTE
For sensors for which the INHIBIT setting has been
set to ON, when you switch to detection mode, the
display alternates between the concentration
display and [INHI.].