26
GB
Start-up, calibration and operation of the burner
5
List of the parameters that can be visualised
(in the sequence
in which they are visualised)
Visualises the general system information.
The list of the parameters that can be visualised is given in
the table below.
To access this level, press the key
“i/reset”
for 1 - 3 s.
Release the key immediately when the display shows
“Info”
.
167
Volumetric delivery of fuel in the unit of measurement
selected
162
Operation time with flame
163
Operation time
164
No. of resettable ignitions
166
Total no. of ignitions
113
Identification code of the burner
107
Software version
102
Control box test date
103
Identification code of the control box
104
Identification number of the group of parameters set
105
Version of the group of parameters
143
Reserved
End
Info Mode
1..3 s
P
m³/h
m³
l
l/h %
D7
7
1
8
/reset
D8
2
7
3
List of the parameters that can be visualised
(in the sequence
in which they are visualised)
Visualises the log of errors and some technical information
regarding the system.
The list of the parameters that can be visualised is given in
the table below.
To access this level, press the
“i/reset”
key for more than 3 s.
Release the key immediately when the display shows
“SEr”
.
954
Flame intensity (%)
121
Manual setting of output
Not defined = automatic operation
922
Position of the servomotors (expressed in degrees,
symbol )
0 = fuel
1 = air
161
Number of errors
701
.
.
.
725
Log of the errors: 701-725.01, Code
Service Mode
> 3 s
P
m³/h
m³
l
l/h %
D7
7
1
9
/reset
D8
2
7
3
Operating procedure in Info and Service Modes
After access to these levels, the display visualises the number of the parameter
(flashing) on the left, and the corresponding value on the right.
If the value is not visualised, press the key
“i/reset”
for 1 - 3 s.
To return to the Parameters List, press the key
“i/reset”
for more than 3 s, or press
simultaneously the keys
“+”
and
“-”
(esc).
To move on to the next parameter, press the key
“+”
or
“i/reset”
for less than 1 s. At
the end of the list, the display visualises
“End”
.
To move back to the previous parameter, press the key
“-”
.
To return to the Normal/Standard Visualisation Mode, press the
“i/reset”
key for
more than 3 s, or press simultaneously keys
“+”
and
“-”
(esc). For a moment the
display will show
“OPErAte”
.
D7
7
2
0
P
m³/h
m³
l
l/h %
From Normal Mode, using the keys of the Operator Panel, it is possible to activate one of the three visualisation/programming modes:
Info Mode (
InFo
)
Service Mode
(Ser)
Service Mode
(Ser)
Visualisation modes
Programming modes
1
2
3
Summary of Contents for RS 100/E MZ
Page 45: ...45 GB Appendix Electrical panel layout A ...
Page 46: ...46 GB Appendix Electrical panel layout A ...
Page 47: ...47 GB Appendix Electrical panel layout A ...
Page 48: ...48 GB Appendix Electrical panel layout A ...
Page 49: ...49 GB Appendix Electrical panel layout A ...
Page 54: ......
Page 55: ......