41
GB
Error
code
Diagnostic
code
Meaning of the system REC27.100A2
Recommended measures
137
#
Internal error – backup / restoration
157
Restoration – OK, but backup < compared with set data of
current system
Restoration successful, but the backup data installed are fewer than those currently present in
the system.
242
Backup – the backup carried out is contradictory
The backup is irregular and cannot be transferred again
243
Backup – the data comparison between the internal
microprocessors is irregular
Repeat the reset and backup
244
The backup data are incompatible
The backup data are incompatible with the current version of the software; the
restoration is not possible
245
Error in access to the parameter Restore_Complete
Repeat the reset and backup
246
Restoration – time-out during logging in EEPROM
Repeat the reset and backup
247
The data received are contradictory
The series of backup data is not valid; restoration is not possible
248
The restoration cannot currently be carried out
Repeat the reset and backup
249
Restoration – interruption caused by inadequate
identification of the burner
The backup has an inadequate identification of the burner and must not be transferred
to the control box
250
Backup – The CRC of a page is not correct
The series of backup data is not valid; restoration is not possible
251
Backup – the identification of the burner is not defined
Define the identification of the burner and repeat the backup
252
After restoration, the pages are still in INTERRUPTION
Repeat the reset and backup
253
The restoration cannot currently be carried out
Repeat the reset and backup
254
Interruption owing to transmission error
Repeat the reset and backup
255
Interruption owing to time-out during the restoration
Carry out a reset, check the connections and repeat the backup
146
#
Time-out of the system automation interface
Refer to the Modbus User Documentation (A7541)
1
Modbus time-out
2
Reserved
165
#
Internal error
166
0
Watchdog reset internal error
167
#
Manual lockout
The control box has been manually blocked (no error)
1
Manual lockout from remote reset command
2
Manual lockout from Operator Panel
3
Manual lockout from PC interface
168 - 171 #
Internal error management
Carry out a reset; if the error arises repeatedly, replace the control box
200
#
System free of errors
No error
201
#
Lockout or error at start
Lockout or error due to lack of parameter settings
1
No operation mode selected
2..3
No fuel train defined
4..7
No curve defined
8..15
Standardisation speed not defined
16..31
Backup / restoration impossible
202
#
Selection of internal operation mode
Redefine the operation mode (parameter 201)
203
#
Internal error
Redefine the operation mode (parameter 201)
Carry out a reset; if the error arises repeatedly, replace the control box
204
Phase
number
Program stop
The program stop is active (no error)
205
#
Internal error
Carry out a reset; if the error arises repeatedly, replace the control box
206
0
Combination of control box and Operator Panel not
allowed
207
#
Compatibility of control box with Operator Panel
0
Obsolete version of
control box
1
Obsolete version of
Operator Panel
208-209 #
Internal error
Carry out a reset; if the error arises repeatedly, replace the control box
240
#
Internal error
Carry out a reset; if the error arises repeatedly, replace the control box
245
#
Internal error
Carry out a reset; if the error arises repeatedly, replace the control box
250
#
Internal error
Carry out a reset; if the error arises repeatedly, replace the control box
Faults - Possible causes - Solutions
6
Summary of Contents for RS 100/E MZ
Page 45: ...45 GB Appendix Electrical panel layout A ...
Page 46: ...46 GB Appendix Electrical panel layout A ...
Page 47: ...47 GB Appendix Electrical panel layout A ...
Page 48: ...48 GB Appendix Electrical panel layout A ...
Page 49: ...49 GB Appendix Electrical panel layout A ...
Page 54: ......
Page 55: ......