Technical description of the burner
3
3.10 Control box for the air/fuel ratio
Introduction
The control box for the air/fuel ratio (hereafter referred to simply
as the control box), that equips the burners of the
RS
range, car-
ries out a series of integrated functions in order to optimise
burner functioning, both for single operation and together with
other units (e.g. double furnace boiler or more than one genera-
tor at the same time).
The basic functions carried out by the control box relate to:
1.
flame control;
2.
the dosage of air and fuel via the positioning (with direct ser-
vocontrol) of the relative valves, excluding the possible play in
the mechanical cam calibration systems;
3.
the modulation of burner output, on the basis of the load
requested by the system, maintaining the pressure or temper-
ature of the boiler at the working values set;
4.
the safety diagnostic of the air and fuel circuits, via which it is
possible to easily identify any causes of malfunctioning.
Further interfaces and computer communication functions (for
remote control or integration in central supervision systems) are
available according to the system configuration.
Technical Data
Fig. 6
D8266
NOTE
The first start-up, like every further operation
for the internal settings of the control box,
requires access by means of a password and
is only to be carried out by personnel of the
Technical Assistance Service who have been
specifically trained in the internal program-
ming of the tool.
The information for the first start-up is given below.
WARNING
Electrical supply
AC 230 V - 15% /
+10%
Frequency
50/60 Hz +/- 6%
Internal fuse
6.3 A T
Operation below the nominal value of electrical supply
Minimum operation value on reduction
of electrical supply below nominal
value
approx. AC 186 V
Minimum operation value on increase
in electrical supply towards nominal
value
approx. AC 195 V
Maximum load of the contacts:
Fan motor relay
Nominal power supply
Nominal current
Output factor
AC 230 V, 50/60 Hz
2 A
cos
ϕ
> 0.4
Alarm exit
Nominal power supply
Nominal current
Output factor
AC 230V, 50/60 Hz
1A
cos
ϕ
> 0.4
Ignition transformer
Nominal power supply
Nominal current
Output factor
AC 230 V, 50/60 Hz
2 A
cos
ϕ
> 0.2
Fuel valves
Nominal power supply
Nominal current
Output factor
AC 230 V, 50/60 Hz
2 A
cos
ϕ
> 0.4
Operator Panel
Nominal power supply
Protection level
Input power
DC 5 V
IP 40
< 50 mW
Length of cables
Electrical supply line AC 230V
Display
max. 100m (100 pF/m)
max. 3m (100 pF/m)
Output regulator
Remote reset button
max. 20m (100 pF/m)
max. 20m (100 pF/m)
Summary of Contents for RS 100/E MZ
Page 45: ...45 GB Appendix Electrical panel layout A ...
Page 46: ...46 GB Appendix Electrical panel layout A ...
Page 47: ...47 GB Appendix Electrical panel layout A ...
Page 48: ...48 GB Appendix Electrical panel layout A ...
Page 49: ...49 GB Appendix Electrical panel layout A ...
Page 54: ......
Page 55: ......