30
GB
5.8
Start-up procedure
Check that the display of the Operator Panel shows request for heat and
“OFF Upr”
: this
means it is necessary to set the modulation curve of the burner.
Access the Parameters Level referring to “
Access procedure with password
”.
The display visualises the parameters group
400;
confirm with the key
“i/reset”
.
The display visualises
“run”
.
Confirm with the key
“i/reset”
: the burner
starts up.
The display visualises in sequence all the various phases and relative times.
The phases are those defined on page 29.
Phase 22:
Start of the fan motor.
As the burner is not fitted with a device to check the sequence of the phases, the motor rotation
may be incorrect. As soon as the burner starts up, go in front of the cooling fan of the fan motor
and check it is rotating anticlockwise. See Fig. 28.
If this is not the case:
³
place the switch of Fig. 28 in position
“0”
and wait for the control box to carry out the
switch-off phase;
³
disconnect the electrical supply from the burner;
³
invert the phases on the three-phase power supply.
Phase 24:
The burner goes to the pre-purging position, the air servomotor opens the damper at 90°.
Phases 80, 81, 82, 83:
These phases relate to the valve seal test (for the burner RS68/E this function is not inserted
in the factory, as it is optional).
Phase 30:
The count of the pre-purging time pre-set in the factory begins.
Phase 36:
The burner goes to the ignition position, point
“P0”
, defined in the table on page 31: the
display visualises the indication
“P0”
flashing. If the value proposed is suitable, confirm.
Otherwise, modify the ignition point (see “
Procedure for inserting and adjusting points on the
modulation curve
”).
Warning:
the values shown in the figure alongside are purely for indication
purposes.
Confirm with the key
“+”.
Phase 38:
The ignition phase begins and the spark goes off.
Phase 40:
The gas valves open (the count of the safety time begins).
Check the presence of the flame from the special inspection window, and the correctness of
the combustion parameters; if necessary, vary the degrees of opening/closing of the air and
fuel servomotors.
If the control box goes into lockout, press the keys
“+”
and
“-”
(esc) simultaneously: the
display visualises alternately the lockout code for flame absence (
c: 4
) and the relative
diagnostic (
d: 3
).
Resolve the problem, referring to Ch. 5.12
.
Reset (see “
Reset procedure
”): the display visualises
“OFF Upr”
.
Repeat the start-up procedure.
Warning:
the values inserted previously remain stored.
D
7
734
P
m³/h
m³
l
l/h %
D
773
6
P
m³/h
m³
l
l/h %
D7
7
4
2
P
m³/h
m³
l
l/h %
DANGER
This operation must be carried out
with the electrical supply discon-
nected.
P
m³/h
m³
l
l/h %
D7
7
4
7
DANGER
P
m³/h
m³
l
l/h %
D7
7
1
2
P
m³/h
m³
l
l/h %
D7
7
1
3
Start-up, calibration and operation of the burner
5
Summary of Contents for RS 100/E MZ
Page 45: ...45 GB Appendix Electrical panel layout A ...
Page 46: ...46 GB Appendix Electrical panel layout A ...
Page 47: ...47 GB Appendix Electrical panel layout A ...
Page 48: ...48 GB Appendix Electrical panel layout A ...
Page 49: ...49 GB Appendix Electrical panel layout A ...
Page 54: ......
Page 55: ......