15
GB
Installation
4.7
Combustion head adjustment
At this point of the installation, the combustion head is fixed
to the boiler as shown in Fig. 13. It is therefore especially
easy to adjust, and this adjustment depends only on the max-
imum output of the burner.
Two adjustments of the head are foreseen:
³
the air adjustment;
³
the gas adjustment.
In the diagram of Fig. 17, find the notch at which to adjust
both air and central gas/air.
Air adjustment
Rotate the screw 2) until the notch you have found corre-
sponds with the front surface 1) of the flange.
Gas adjustment (RS 70-100-130/E MZ)
Loosen the 4 screws and turn ring 5) until the notch identified
is aligned with index 6).
Tighten the 3 screws 4) fully down.
Gas adjustment (RS 190/E - RS 250/E MZ)
When the burner is installed for maximum burner output
≤
1300 Mcal/h (approx. 1500 kW) fit the discs 1)-2)(Fig. 16),
supplied as part of the standard equipment, removing the
internal tube 3)(Fig. 16). If the mains gas pressure is low, the
head can be left in the standard set-up, limiting the modula-
tion minimum to 450 Mcal/h (approx. 520 kW).
Example
RS 70/E MZ, burner output = 581 kW.
According to diagram Fig. 17 the gas and air adjustments for
this output are carried out on notch 3.
NOTE
The diagram indicates the optimum adjustment for a type of
boiler according to Fig. 4.
Important
To facilitate adjustment, loosen the screw 3),
adjust and then lock.
Fig. 16
2
3
1
D8084
2
1
2
1
3
4
5
6
D8039
RS 70-100-130/E MZ
RS 190/E - RS 250/E MZ
Fig. 15
CAUTION
No
. of
Notc
he
s
Maximum output of burner
D8040
Fig. 17
Maximum burner output
10
1200
9
7
5
3
1
1900
1700
1500
1300
1100
8
6
4
2
0
kW
Mcal / h
1400
1600
1800
2000
2200
2800
2600
2400
2100
2300
2500
RS 250/ E
RS 190/ E
No. of
No
tch
e
s
D720
RS 70/E MZ
RS 130/E MZ
RS 190/E
RS 100/E MZ
RS 250/E MZ
in progress
4
Summary of Contents for RS 100/E MZ
Page 45: ...45 GB Appendix Electrical panel layout A ...
Page 46: ...46 GB Appendix Electrical panel layout A ...
Page 47: ...47 GB Appendix Electrical panel layout A ...
Page 48: ...48 GB Appendix Electrical panel layout A ...
Page 49: ...49 GB Appendix Electrical panel layout A ...
Page 54: ......
Page 55: ......