Visualises and allows you to modify/program the complete list of
parameters, shown in the table on page 34.
The factory-set parameters are not visible.
The parameters level is subdivided into groups:
To access this level, refer to “
Access procedure with password
”.
Once the access procedure has been carried out, the display will
show
“PArA”
for a few seconds.
Select the group of parameters with keys
“+“
and
“-“
, and con-
firm by pressing the
“i/reset”
key.
Within the group you have chosen, scroll through the list with the
keys
“+“
and
“-”
. At the end of the list, the display visualises
“End“
.
To return to Normal visualisation mode, simultaneously press the
keys
“+”
and
“-”
(esc) twice.
To modify a parameter, refer to “
Parameter modification proce-
dure
”.
Parameters Mode
100: ParA
General parameters
Information and identification data of the system.
200: ParA
Checks on the Burner
Type of operation, intervention and safety times
of the various phases.
400: Set
Air/Fuel modulation curve
Setting of Air/Fuel adjustment points
500: ParA
Positioning of Servomotors
Choice of positions of the air/fuel servomotors in
the various phases.
600: ParA
Servomotors
Setting and addressing of the servomotors.
700: HISt
Log of the errors
Choice of different visualisation modes for the
errors log.
900: dAtA
Process information
Visualisation of information for the remote man-
agement of the burner.
All the parameters are checked in the factory.
Modification/tampering may compromise the good
operation of the burner and cause injury to people
or damage to things. In any case, modifications
must be carried out by qualified personnel.
P
m³/h
m³
l
l/h %
D7
7
2
2
DANGER
Start-up, calibration and operation of the burner
5
Access procedure with password
Press the keys
“F”
and
“A”
simultaneously for 1s:
for a moment the display
will show
“CodE“
, and
immediately after you will
see 7 dashes, the first one
flashing.
With the keys
“+”
and
“–”
select the first character of
the password (letter or
number), and confirm by
pressing the key
“i/reset”
.
P
m³/h
m³
l
l/h %
P
m³/h
m³
l
l/h %
D7
7
2
1
D
7
735
%
l/h
l
m³ m³/h
P
D7
7
4
4
Once you have confirmed,
the sign
“–”
will appear.
Continue in the same way
for the other characters.
After inserting the last
character of the password,
confirm by pressing the
key
“i/reset”
: if the pass-
word inserted is correct
you will see
“PArA“
for a
few seconds, then you can
access the various groups
of parameters.
With the keys
“+”
and
“–”
select the group you
require.
If the password inserted is
incorrect, the message
“Error“
will appear for a
moment.
It is then necessary to
repeat the procedure.
The password must only be communicated to the
qualified personnel or the Technical Assistance
Service, and must be kept in a safe place.
D7
7
2
2
D
7
736
P
m³/h
m³
l
l/h %
P
m³/h
m³
l
l/h %
D7
7
4
5
P
m³/h
m³
l
l/h %
DANGER
Summary of Contents for RS 100/E MZ
Page 45: ...45 GB Appendix Electrical panel layout A ...
Page 46: ...46 GB Appendix Electrical panel layout A ...
Page 47: ...47 GB Appendix Electrical panel layout A ...
Page 48: ...48 GB Appendix Electrical panel layout A ...
Page 49: ...49 GB Appendix Electrical panel layout A ...
Page 54: ......
Page 55: ......