1
WAYNE COMBUSTION SYSTEMS
801 GLASGOW AVE.
FORT WAYNE, IN 46803
PHONE: (260) 425-9200
(855) WAYNECS
(800) 443-4625
FAX: (260) 424-0904
www.waynecombustion.com
EHG
Manual 63537-001 | Revision K | Publication Date: 6/9/2014
Gas Burner
SPECIFICATIONS
De-rate maximum input for altitude over 2000 ft. (610 m) by 4% each 1000 ft. (305 m) above sea level.
Ignition:
15.6k VAC Direct Spark Ignition. Standard burners are shipped with the ignition transformer mounted to the burner. If the
transformer is to be remotely mounted, the ignition wire must not exceed 36” (914.4mm) per UL795.
Supply Line Pressure Required:
Natural or Propane 6” w.c. (1494 pa) Minimum,14”
w.c. (3487 Pa) Maximum
INSTALLATION OF BURNER
INSTALLATION OF THE BURNER MUST BE DONE BY A QUALIFIED INSTALLER IN ACCORDANCE WITH REGULATIONS OF
THE NATIONAL FUEL GAS CODE ANSI Z223.1/NFPA 54, AND IN COMPLETE ACCORDANCE WITH ALL LOCAL CODES AND
AUTHORITIES HAVING JURISDICTION.
INCORRECT INSTALLATION, ADJUSTMENT, OR MISUSE OF THIS BURNER WILL VOID THE WARRANTY and COULD
RESULT IN DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE.
A QUALIFIED INSTALLER IS THE PERSON WHO IS RESPONSIBLE FOR THE INSTALLATION AND ADJUSTMENT OF THE
EQUIPMENT AND WHO IS LICENSED TO INSTALL GAS-BURNING EQUIPMENT IN ACCORDANCE WITH ALL CODES AND
ORDINANCES.
THESE INSTRUCTIONS SHOULD BE AFFIXED TO THE BURNER
OR ADJACENT TO THE HEATING APPLIANCE.
EHG
425 MBtu/hr (125 kW)
700 MBtu/hr (205 kW)
120 VAC / 60 Hz 1 Phase
24 VAC Single-Rod Gas Primary
Adjustable Flange Standard
4 inches (101.6 mm)
5 inches (127 mm) Maximum with 6 inch
(152 mm) Air Tube.
7 inches (178 mm) Maximum with 9 inch
(228 mm) Air Tube.
10 inches (254 mm) Maximum with 12 inch
(305 mm) Air Tube.
13 inches (381 mm) Maximum with 15 inch
(381 mm) Air Tube.
Burner Model:
Minimum Input:
Maximum Input:
Standard Voltage:
Flame Safety:
Mounting Flange:
Air Tube Diameter:
Air Tube Insertions:
Summary of Contents for EHG
Page 16: ...16 EHG POWER GAS BURNER WITH HONEYWELL S89F GAS PRIMARY AND GAS TRAIN ASSEMBLY Figure 11...
Page 35: ...35 Cover Manifold Orifice Assembly Figure 27...
Page 36: ...36 Burner Exploded and Assembled Views 64021 003 Figure 28...
Page 38: ...38 Control Box Assembly 63479 004 or 63479 005 Figure 29...
Page 39: ...39 Control Box Assembly 63479 004 or 63479 005 Figure 29 Continued...
Page 41: ...41 Gas Train Assembly with Regulator 63527 001 Figure 31...
Page 44: ...44 Flange 20614 Figure 33...
Page 47: ...47 NOTES...