11
The 1/8″ NPT pressure tap for manifold pressure measurement is located on the side of the burner’s manifold pipe (see
figure 4). Use a “u”-tube manometer or dial type pressure gauge, scaled from 0″w.c. to 15.0″ w.c. (3736.5Pa) to read
pressure.
Figure 7
I. GAS PRESSURE SWITCHES
MOUNTING
All switches can be mounted in either horizontal or vertical position. Switches should be reasonably level but do not
require accurate leveling.
Switches have been factory calibrated and tested for leaks. However, it is recommended that the switch body, gas pipe
inlets and connections be soap bubble tested for leaks after installation.
OPERATION
Low Gas Pressure Models
Low gas pressure switches break the electrical circuit on pressure drop at the point when gas pressure becomes lower
than the indicated set pressure.
Before the manual reset button can be properly latched, gas pressure in the chamber must be higher than the indicated
setting.
High Gas Pressure Models
High gas pressure switches break the electrical circuit when pressure rises above the indicated preset pressure.
Range Adjustment - All Models
To adjust gas pressure cut-off setting, remove the cover. Turn the range scale adjustable knob to increase pressure
setting or decrease pressure setting. Install cover and tighten the cover screws to prevent tampering. Proper adjustment
of the high and low gas pressure switches is explained in section II.
Regulator Cap
Summary of Contents for EHG
Page 16: ...16 EHG POWER GAS BURNER WITH HONEYWELL S89F GAS PRIMARY AND GAS TRAIN ASSEMBLY Figure 11...
Page 35: ...35 Cover Manifold Orifice Assembly Figure 27...
Page 36: ...36 Burner Exploded and Assembled Views 64021 003 Figure 28...
Page 38: ...38 Control Box Assembly 63479 004 or 63479 005 Figure 29...
Page 39: ...39 Control Box Assembly 63479 004 or 63479 005 Figure 29 Continued...
Page 41: ...41 Gas Train Assembly with Regulator 63527 001 Figure 31...
Page 44: ...44 Flange 20614 Figure 33...
Page 47: ...47 NOTES...