background image

FAMILY CONDENS IS E

4

ENGLISH

5

2.1 

Safety devices

The  FAMILY CONDENS IS E boiler is equipped with the following 
safety devices:
Safety valve that intervenes in the event of excessive hydraulic pres-
sure (max 3 bar).
Water circuit diagnosis which safeguards the boiler in the event of 
insufficient circulation or lack of water. The electronics of the boiler, 
by comparing the temperature read by the outlet and return sensors 
(circulation analysis) and the rise rate of the output temperature (no 
water analysis) ensures the safety lockout of the appliance.
Flue gas probe: this intervenes (putting the boiler in safety stop 
mode) if the temperature of the combustion products exceeds the 
maximum operating temperature of the discharge pipes.
Flue gas safety evacuation system incorporated in the pneumatic 
operation of the gas valve subject to the premix burner The gas valve 
is opened based on the quantity of air pushed by the fan.
This implies that, if the flue gases exhaust circuit
is blocked, the air flow is cancelled and the valve does not have the 
ability to open.
Furthermore, the float present in the siphon prevents any passage of 
the flue gases from the condensation discharge.
Condensate discharge obstruction safety device that via a con-
densate level sensor blocks the boiler if the level of condensate in the 
heat exchanger exceeds the limit allowed
Over-temperature safety device on both the delivery and return 
lines, with dual probe (limit temperature 95°C).
Fan safety that, through a Hall effect revolution counter, constantly 
monitors the rotation speed of the fan.

  The intervention of the safety devices indicates a boiler mal-

function, therefore immediately contact the Riello Technical 
Assistance Service It is therefore possible to try and put the 
boiler back in service after a short wait (see chapter on "First 
commissioning").

  The boiler must not be put in service, even temporarily, with 

non-operating or tampered safety devices.

  Replacement of safety devices must be performed by the Ri-

ello Technical Assistance Service, by exclusively using original 
manufacturer components and referring to the spare parts list 
accompanying the boiler. After carrying out the repair, perform 
an ignition test.

2.2 

Circulator setting

Circulator residual discharge head
The boilers is equipped with an already hydraulically and electrically 
connected circulator, whose useful available performance is indicated 
in the graph (fig. 1-2-3-4).

The circulator is factory set with discharge head of 6 meters.

The boiler is equipped with an anti-blocking system which starts 
up an operation cycle after every 24 hours of stop, with the mode 
selector in any position.

  The "anti-locking" function is only activated when the boiler is 

electrically powered.

  It is strictly forbidden to operate the circulator without water.

Where there is the need to use a different curve, the desired level can 
be selected on the circulator.
The main characteristics and how to set the desired operation are 
described below.

User interface
The user interface is made up of a button (A), a two-coloured red / 
green LED (B) and four yellow LEDs (C) arranged in a row (fig. 5). 
The user interface allows to view the operating performance (oper-
ating status and alarm status) and set the operating mode of the 
circulator.

The performance, indicated by LEDs (B) and (C) are always visible 
during the normal operation of the circulator, while the settings are 
made by pressing button (A).

Indication of the operating status

When the circulator is operating, LED (B) is green. The four yellow 
LEDs (C) indicate the consumption of electric power (P1) as shown 
in the following table

LED status

Status

CIRCULATOR

Consumption in % of

P1 MAX (*)

Green LED on +
1 yellow LED on

Minimum operation

0÷25

Green LED on +

2 yellow LEDs on

Minimum-medium 

operation

25÷50

Green LED on +

3 yellow LEDs on

Medium-maximum 

operation

50÷75

Green LED on +

4 yellow LEDs on

Maximum operation

100

(*) For the output (P1) absorbed by the circulator, refer to that indicat-
ed in the “Technical Data” table.

Indication of the alarm status
If the circulator has detected one or more alarms the bi-colour LED 
(B) is red. The four yellow LEDs (C) indicate the type of alarm as 
shown in the following table.

LED status

ALARM 

description

Status

CIRCULATOR

Possible 

REMEDY

Red LED

on + 

1 Yellow LED 

on (LED 5)

The crankshaft 

is blocked

Start attempt 

every 1.5 

seconds

Wait or 

unblock the 

crankshaft

Red LED

on + 

1 yellow LED 

on (LED 4)

Low input voltage

Warning only. 
The circulator 

continues to 

operate

Check the 

input voltage

Red LED

on + 

1 yellow LED 

on (LED 3)

Electrical power 
supply failure or 

circulator fault

The circulator 

has stopped

Check the 

electrical 

supply or 

replace the 

circulator

  If there are multiple alarms, the circulator displays the highest 

priority alarm only.

Display of the active settings
With the circulator powered, the active configuration of the circulator 
can be viewed by briefly pressing the button (A). The LEDs indicate 
the active settings.
No change to the configuration of the circulator can be made at this 
stage. Two seconds after of pressing the button (A), the user inter-
face returns to the normal display of the operating status.

Key lock function
The key lock function is designed to prevent an accidental change of 
settings or misuse of the circulator.
When the lock function is activated, the prolonged pressing of button 
(A) is inhibited. This prevents the user from entering the setting sec-
tion of the circulator operating mode.
The enabling/disabling of the key lock function is made by pressing 
button (A) for more than 10 seconds. During this step, all LEDs (C
flashes for 1 second (fig. 6).

Variation of the operating mode
In normal operation the circulator operates with the factory setting or 
the last setting made.
To vary the configuration:
-  Make sure the key lock function is disabled.
-  Press button (A) for more than 2 seconds until the LEDs start blink-

ing. Pressing button (A) briefly within a period of no more than 10 
seconds, the user interface will display the next settings. The vari-
ous settings available will appear in a cyclic sequence.

-  If the button (A) is not pressed, the last setting will be stored (fig. 7).
-  Pressing button (A) allows to go back to the "display of the active 

settings" and verify that LEDs (B) and (C) indicate, for 2 seconds, 
the last setting made.

Summary of Contents for FAMILY CONDENS 2.5

Page 1: ...FAMILY CONDENS 2 5 3 0 3 5 IS E EN INSTALLER AND USER MANUAL HU TELEP T SI S HASZN LATI K ZIK NYV...

Page 2: ...n l term kek k rnyezetbar t tervez s r l 2010 30 EU ir nyelv az energi val kapcsolatos term kek energia fogyaszt s nak c mk z ssel t rt n jel l s r l 811 2013 EU felhatalmaz son alapul rendelet 813 20...

Page 3: ...FAMILY CONDENS IS E 3...

Page 4: ...l In this case ventilate the room by opening the doors and windows close the fuel shut off device promptly contact the Riello Technical Assistance Centre or other professionally qualified personnel It...

Page 5: ...on A a two coloured red green LED B and four yellow LEDs C arranged in a row fig 5 The user interface allows to view the operating performance oper ating status and alarm status and set the operating...

Page 6: ...direct mode systems typical of the re placement in which the boiler is not using the temperature control and where a calculated T can be set Working at a constant outlet temperature and with the envi...

Page 7: ...alkalinity less than 50 ppm Total hardness less than 35 F Sulphur ions None Ammonia ions None Silicon ions less than 20 ppm The manufacturer is not liable for any damage resulting from the incorrect c...

Page 8: ...oard covers then open them by sliding them in the direction shown by the arrows SPECIAL SYSTEMS The boiler is able to control an additional circulator connected hy draulically as shown in the followin...

Page 9: ...ed with the specific ac cessory kit for condensing boilers Maximum length of twin pipe 80 mm pressure drop 45 curve 90 curve 2 5 IS E 3 0 IS E 50 50m 1 m 1 5m 3 5 IS E 38 38m Straight length means wit...

Page 10: ...ting from the failure to channel the condensate 3 13 Installation of collective positive pressure smoke pipes The collective smoke pipe is a flue gases system suitable for col lecting and expelling co...

Page 11: ...pens 6 Carry on with the sequence until only water leaks out of the man ual air vent valve and the air flow has stopped now close the manual air vent valve 7 Check the system pressure level is correct...

Page 12: ...and turn the encoder A The large digits will light up on the display indicating the selected temperature value After a few seconds the display will again show the outlet tempera ture actually measured...

Page 13: ...1x3 40 flap 1x3 25 free mm FAMILY CONDENS 3 0 IS E Diameter of the main burner nozzles 63 63 mm Burner length 110 110 mm Number of diaphragm holes 2 2 nr Diaphragm holes diameter 1x4 30 flap 1x4 20 f...

Page 14: ...it If no confirmation is given within 10 seconds the value is not stored and the previous one is indicated again Setting the password The programming of the parameters is accessed by pressing the key...

Page 15: ...5 NOT USED 6 BAG2 MIX 7 NOT USED 8 NOT USED 1 21 MAXIMUM HEATING SET POINT C 40 80 80 22 MINIMUM HEATING SET POINT C 20 39 20 23 MAXIMUM HEATING FAN SPEED Range Rated adjustment rpm NG LPG 2 5 IS E 4...

Page 16: ...VERY FAST 255 VERY SLOW 20 85 SEMI AUTOMATIC CHARGE 0 DISABLED 1 ENABLED 1 86 PRESSURE OF SEMI AUTOMATIC CHARGE ON bar 0 4 1 0 0 6 87 PARAMETER CAN NOT BE USED IN THIS MODEL DO NOT MODIFY THE PROGRAMM...

Page 17: ...22 There are two parameters that allow to limit the delivery tempera ture produced automatically by the THERMOREGULATION function based on the type of system see table System type T max T min Cast iro...

Page 18: ...oiler turns on according to the programmed settings With the contact open the thermoregulation of the boiler is placed on NIGHT at 16 C and calculates the delivery temperature according to the new con...

Page 19: ...t on DHW circuit probe 60 The fault code is only displayed in standby Fault J0 card interface connection check that the electrical con nections are correct If the fault persists after the control cont...

Page 20: ...ssary the system s pressure Analyze combustion Compare results with the product s specification Any loss in performance must be identified and corrected by finding and eliminating the cause Make sure...

Page 21: ...ter HP press the ENTER key to be able to modify the parameter value The maximum fan speed is linked to the type of gas and the boiler output table 1 Turn the encoder until the desired value is reached...

Page 22: ...ing combustion checks TABLE 5 MAXIMUM NUMBER OF FAN ROTATIONS return fault METHANE GAS G20 LIQUID PROPANE GAS G31 2 5 IS E 45 45 rpm 3 0 IS E 51 49 rpm 3 5 IS E 53 54 rpm POSSIBILITY OF ADJUSTING THE...

Page 23: ...00 3600 4000 4400 4800 5200 5600 6000 6400 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Giri ventilatore r p m Portatatermica kW Curva portata termica giri ventilatore Family Condens 25 E 0 10 20 30 40 50...

Page 24: ...Emissioni CO s a p p m Portatatermica kW Curva portata termica emissioni CO CaldaiaFamily Condens 3 0 E Thermal output curve no of fan rotations MTN 3 0 IS Heat output kW Fan rotations r p m G20 800...

Page 25: ...140 150 160 170 180 190 200 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 Emissioni CO s a p p m Portatatermica kW Curva portata termica emissioni CO sa CaldaiaExclusive Green E 35 800 12...

Page 26: ...he teeth DO NOT FORCE loosen the plastic venturi B and press from the opposite side until it is completely extracted from the aluminium body replace the plastic venturi with the one contained in the k...

Page 27: ...cts Do not use fuels and or sponges soaked in abrasive solutions or powder detergents Internal cleaning Before starting internal cleaning operations Close the gas shut off valve Close the system taps...

Page 28: ...mell of fuel or unburned fuel In this case Ventilate the room by opening the doors and windows Close the fuel shut off device promptly contact the r Technical Assistance Centre or other professionally...

Page 29: ...ature To adjust the temperature of the outlet water press the heating tem perature adjustment key A The two digits will no longer show the temperature measured instan taneously by the probe but the te...

Page 30: ...lies hot water for the preparation of the domestic water During this operation the icon will flash on the display MODE C only heating storage tank with probe to adjust the tem perature of the domestic...

Page 31: ...ored outlet temperature by 5 C Memory repeats the cycle until the ambient temperature set on the ambient thermostat is reached or until the maximum permitted tem perature is reached Thanks to this aut...

Page 32: ...no electricity supply Check that the power supply plug of the appliance if present is correctly in serted the main system switch is positioned on ON If the switch on operation is still unsuccessful co...

Page 33: ...sufficient system pressure 79 Outlet return differential The RESET and icons light up and the alarm code appears table 3 CALL THE TECHNICAL SERVICE CODE DESCRIPTION 21 Flue gas probe 28 Outlet return...

Page 34: ...38 Sm3 h 0 31 0 35 0 39 kg h DHW minimum gas capacity 0 30 0 34 0 38 Sm3 h 0 31 0 35 0 39 kg h Residual discharge head of boiler without pipes 80 125 160 Pa Collective smoke pipes under pressure with...

Page 35: ...Family Condens 3 0 IS E Family Condens 3 5 IS E Unit Seasonal space heating energy efficiency class A A A Water heating energy efficiency class Rated heat output Pnominal 20 25 29 kW Seasonal space he...

Page 36: ...k t zel anyaggal rammal s v zzel m k dnek be kell tartani n h ny alapvet biztons gi szab lyt mint p ld ul Tilos a kaz nt gyerekeknek vagy k pzetlen szem lyeknek seg ts g n lk l haszn lniuk Ha g zszago...

Page 37: ...nye a grafikonon l that 1 2 3 4 bra A keringtet gy rilag be ll tott emel nyom s g rb je 6 m ter A kaz n el van l tva egy blokkol sg tl rendszerrel is amely 24 r nk nt egyszer elind t egy zemel si cikl...

Page 38: ...param terbe ll tsa be a param tert 60 2 V LTOZTATHAT SEBESS G KERINGTET KONSTANS T ZEMM DDAL 2 P90 40 Ebben az zemm dban a telep t a T rt ket gy ll tja be hogy lland maradjon az el remen s a visszat r...

Page 39: ...sz tse el A t zel anyagot biztos t vonalat s az esetleges tart lyt LPG az erre vonatkoz speci lis szab lyoz snak megfelel en k sz ts k el A t gul si tart ly biztos tsa a rendszerben l v folyad k t gu...

Page 40: ...kat Laz tsuk meg a k belvezet csavarj t vezess k be az elektromos vezet ket s r gz ts k az elektromos kapcsokba A h m rs klet rz kel elektromos vezet k nek bek t s t a kaz nba az Elektromos bek t sek...

Page 41: ...90 k ny kn l 2 5 IS E 3 0 IS E 7 80 m 1 3 m 1 6 m 3 5 IS E 7 85 m F GG LEGES koaxi lis cs egyenes hossz s ga 60 100 mm raml si vesztes g 45 90 k ny kn l 2 5 IS E 3 0 IS E 8 80 m 1 3 m 1 6 m 3 5 IS E 8...

Page 42: ...sz Line ris megfelel je m terben 80 m 45 50 os kanyarulat 12 3 90 50 os kanyarulat 19 6 Hosszabb t 0 5 m 50 6 1 Hosszabb t 1 0 m 50 13 5 Hosszabb t 2 0 m 50 29 5 3 12 A rendszer felt lt se s r t se 2...

Page 43: ...zerelve 32 bra Javaslatok a f t si rendszer s a kaz n megfelel l gtelen t s hez Az els felszerel s illetve rendk v li karbantart s alkalm val aj nlatos az al bbi m veletsort elv gezni 1 K t vagy h rom...

Page 44: ...si jelz sen vil g t vonalka fel vagy lemegy A korrig l s 5 s 5 komfortfokozat k z tt t rt nhet Ezek a korrekci k el s ut szezonban fontosak amikor a g rbe sz m tott rt ke t l alacsony lehet ez rt megn...

Page 45: ...szerfalat s forgassa el refel Laz tsa meg k t fordulattal a g zszelep el tt l v nyom scsatlakoz csavarj t s csatlakoztassa a manom terhez Helyezze ram al a kaz nt a berendez s k zponti kapcsol j nak...

Page 46: ...t s gy a k sz l k jobban hozz igaz that az egyedi ig nyekhez mind a f t si rendszer jellemz ihez mind pedig a felhaszn l i egyedi ig nyekhez A programozhat param terek a t bl zatban l that k A param t...

Page 47: ...1 ON 2 T VOLI PANEL Z NASZELEPEK 3 BAG2 4 NEM HASZN LHAT 5 NEM HASZN LHAT 6 BAG2 MIX 7 NEM HASZN LHAT 8 NEM HASZN LHAT 1 21 MAXIM LIS F T SI SET POINT C 40 80 80 22 MINIM LIS F T SI SET POINT C 20 39...

Page 48: ...SN L NE M DOS TSA A PROGRAMOZ ST 6 65 K LS SZONDA REAKCI K PESS GE 0 NAGYON GYORS 255 NAGYON LASS 20 85 F LAUTOMATIKUS BET LT S 0 KIIKTATVA 1 BEIKTAT 1 86 F LAUTOMATIKUS BET LT SI NYOM S ON bar 0 4 1...

Page 49: ...kusan megfelel hat rok k z tt tartsa a kaz n Rendszer t pusa T max T min nt ttvas radi torok 80 60 H sug rz panelek 50 30 Ventil toros radi tor 50 30 Padl 40 20 A 21 PARAM TER hat rozza meg a maxim li...

Page 50: ...n lata eset n az 52 PARAM TERT az 51 n l le rtak szerint kell be ll tani 10 20 30 40 50 60 70 80 90 20 15 10 5 0 5 10 15 20 Curva climatica GIORNO Curva climatica NOTTE JSZAKAI H M RS KLET CS KKENT S...

Page 51: ...mbot am g a norm l m k d s helyre nem ll K d Hiba le r sa RESET ikon Ikon 10 LE LL S L NGHI NY MIATT D IGEN NEM 11 ROSSZ L NG D NEM IGEN 12 JB LI K S RLET FOLYAMATBAN T NEM NEM 13 G Z BEMENTI MIN NYOM...

Page 52: ...kiv lt okot majd meg kell sz ntetni azt Ellen rizze hogy az els dleges h cser l tiszta e s nincs e rajta lerak d s illetve nincs e elt m dve sz ks g eset n tiszt tsa meg A helyes m k d s biztos t sa...

Page 53: ...2 10 HP SP LP 23 24 param tereket csak k pes tett szakember m dos thatja s kiz r lag abban az esetben ha az felt tlen l sz ks ges A gy rt elh r t minden felel ss get a param terek t ves megv ltoztat s...

Page 54: ...tert Nyomja meg az ENTER gombot a param ter v ltoztat shoz val hozz f r shez Forgassa haszn lati melegv z h m rs klet szab lyoz gombj t a ventil tor maxim lis sebess g nek v ltoztat s hoz 5 t bl zat V...

Page 55: ...400 2800 3200 3600 4000 4400 4800 5200 5600 6000 6400 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Giri ventilatore r p m Portatatermica kW Curva portata termica giri ventilatore Family Condens 25 E 0 10...

Page 56: ...issioni CO s a p p m Portatatermica kW Curva portata termica emissioni CO CaldaiaFamily Condens 3 0 E H teljes tm ny g rbe ventil tor fordulatsz ma 3 0 IS H teljes tm ny kW Ventil tor fordulatsz m f p...

Page 57: ...110 120 130 140 150 160 170 180 190 200 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 Emissioni CO s a p p m Portatatermica kW Curva portata termica emissioni CO sa CaldaiaExclusive Green...

Page 58: ...eljesen ki nem j n az alum nium h zb l Cser lje ki a m anyag venturit a k szletben tal lhat ra Szerelje ssze a kever t a sz rnyakkal v zszintes helyzetben s a t vtart rug kkal 120 ban ahogy az br n l...

Page 59: ...z n ramell t s t a f kapcsol t OFF ll sba forgatva Z rja el a rendszer csapjait s engedje le a kaz n f t k ri viz t H zza ki a bypass teste burkolat nak r gz t klipp t 1 H zza ki a bypass test nek fed...

Page 60: ...n lni vagy bekapcsolni ha f t anyag vagy g sterm k illatot rez Ebben az esetben szell ztesse ki a helyis get az ajt kat ablakokat kinyitva z rja el a t zel anyag lez r k sz l ket halad ktalanul h vja...

Page 61: ...rs klet be ll t sa Az el remen v z h m rs klet nek be ll t s hoz meg kell nyomni a f t si h m rs kletet be ll t gombot A K t k dn l elt nik a szonda ltal m rt pillanatnyi h m rs klet s villogni kezd a...

Page 62: ...melegv zt rol termoszt tja h ig nyt jelez a kaz n melegvizet juttat a t rol ba hogy az ott t rolt vizet felmeleg tse E m velet ideje alatt a kijelz n villog a jel C ESET csak f t s k ls melegv zt rol...

Page 63: ...n veli a mentett el remen h m rs kletet A Memory addig ism tli a ciklust am g a h m rs klet el nem ri a belt ri termoszt ton be ll tott rt ket vagy a maxim lisan megengedett h m rs kletet Ennek a fun...

Page 64: ...nem megjelennek a RESET gomb s a N A hib k kik sz b l se V rjon minden esetben kb 10 m sodpercet miel tt vissza ll tja a rendes m k d st Az elv gzend m veletek a k vetkez k 1 Csak a ikon jelenik meg...

Page 65: ...0 59 Elektronikus k rtya 70 Primer szonda r vidz rlat nyitva 72 Visszat r szonda r vidz rlat nyitva 80 Rendszerhiba 82 Rendszerhiba P Rendszeres tervezett karbantart s M VELETEK 1 V 2 V T m t alkatr s...

Page 66: ...g zfogyaszt s f t s 0 30 0 34 0 38 Sm3 h 0 31 0 35 0 39 kg h Min g zfogyaszt s HMV 0 30 0 34 0 38 Sm3 h 0 31 0 35 0 39 kg h Kaz n marad k emel nyom sa cs vek n lk l 80 125 160 Pa K z s f stcs nyom s...

Page 67: ...ly A A A V zmeleg t si energiahat konys gi oszt ly N vleges teljes tm ny Pn vleges 20 25 29 kW Szezon lis helyis gf t si hat sfok s 94 94 93 Hasznos h teljes tm ny M rt h teljes tm nyen s magas h m r...

Page 68: ...FAMILY CONDENS IS E 68 M R AF G AC 9 11...

Page 69: ...Mixer 24 T gul si tart ly 25 Als leveg szell z szelep 26 Keringet szivatty 27 H rom ll s szoleonid szelep 28 Elt voz gy jt EN Boiler functional elements 1 Gas valve 2 Discharge valve 3 Pressure transd...

Page 70: ...FAMILY CONDENS IS E 70 A C B D 1 2 3 4 5 7 9 11 12 13 10 F E 6 8 14 15...

Page 71: ...Expansion vessel 12 Lower air vent valve 13 Circulator 14 3 way valve 15 Water tank available on request HU Hidraulikus k r A F t si el remen B F t si visszat r C T rol el remen g D T rol visszat r g...

Page 72: ...tank with probe if connected 1 2 4 8 7 6 5 3 HU Vez rl panel 1 Info GOMB Azt a funkci t aktiv lja amely lehet v teszi a kaz n bizonyos m k d si inform ci ihoz val hozz f r st 2 MEMORY GOMB Aktiv lja a...

Page 73: ...sition of the set domestic water temperature the position in relation to the maximum and min imum 15 Domestic hot water flame on indicates the burner is on fol lowing a domestic hot water heat request...

Page 74: ...TSC2 blu marrone E A 2 1 3 4 J10 2 1 3 5 4 1 2 4 3 VALVOLA GAS OPE OPE blu marrone rosa 3V 2 N J9 nero san blu 1 risc marrone risc 3 san 7 2 1 4 3 5 6 9 8 10 blu marrone P2 M2 3 1 2 5 4 blu marrone L...

Page 75: ...l board for external connections in high voltage F External fuse 3 15A F HU T bbvezet kes bek t si rajz L N POLARIZ L S AJ NLOTT Blu K k Marrone Barna Nero Fekete Rosso V r s Bianco Feh r Viola Lila G...

Page 76: ...on the terminal board The contacts of the ambient thermostat and hourly timer must be sized for 230 Volt A B C E G D C T A F F HU Nagyfesz lts g csatlakoz soke A SZOBATERMOSZT T VAGY KRONOTERMOSZT T B...

Page 77: ...the figure T B T Low temperature thermostat S E External probe T BOLL storage tank thermostat F 3 15A F fuse HU Kisfesz lts g csatlakoz sok Az br n l that m don csatlakoztassa a kisfesz lts g felhasz...

Page 78: ...UPM3 FLEX 15 60 P90 60 mbar A E 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 1300 Prevalenza mbar Portataimpianto l h Prevalenzaresidu...

Page 79: ...Prevalenza Impianto UPM3 FLEX 15 50 P90 60 A E 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 0 100 200 300 400 500 600 700 800 900 1000 Prevalenza mbar Portataimpianto l h Prevalenzaresidu...

Page 80: ...stato di funzionamento x 7 m 6 m 5 m 4 m LED 1 rosso LED 2 giallo LED 3 giallo LED 4 giallo LED 5 giallo 4 3 2 1 valore settato da fabbrica EN A Operating functioning signal B Setting signal C Setting...

Page 81: ...Template HU A Tart lap B Sablon fig 13 A B C B A 218 5 227 C EN A Concentric duct for fumes outlet Air intake B Fumes duct for intake in environments C 60 80 adaptor HU A KONCENTRIKUS CS F STG ZELVEZE...

Page 82: ...19 M G R SC A fig 21 A B C D EN A Split ducts for fumes outlet Air intake HU A OSZTOTT CS VEK F STG ZELVEZET L GELSZ V S EN A Discharge manifold HU A Elvezet csatlakoz EN A CH delivery B Hot water C C...

Page 83: ...ldaia EN A Connect the supplementary pump to the 2 poles terminal board in the area dimensioned for V 230 Volt B Boiler C Boiler pump D Supplementary pump E Hydraulic separator HU A Csatlakoz a kieg s...

Page 84: ...e 90 80 mm riduzione 80 60 mm curva 90 60 mm Lunghezza fig 27 fig 28 E B A C EN A Smoke pipe for ducting 60 m B Length C Bend 90 80 mm D Reduction 80 60 mm E Bend 90 60 mm HU A k m ny cs bek t shez 60...

Page 85: ...25 E lunghezzamassimatubi 80 mm C B A 3 5 IS E C B 0 10 20 30 40 50 60 70 0 10 20 30 40 50 60 70 80 90 100 Lunghezza tubo scarico fumi m Lunghezza tubo aspirazione aria m CaldaiaExclusive Green E 35 l...

Page 86: ...FAMILY CONDENS IS E 86 fig 29 fig 32 fig 31 fig 30 B A C D...

Page 87: ......

Page 88: ...Cod 20120920 05 16 Ed 0...

Reviews: