FAMILY CONDENS IS E
12
ENGLISH
13
1
B
A
Supply gas pressure check
- Press button 1,
, to turn off the boiler
- Unscrew the fixing screws (C) of the connections cover
- Take out the connections cover by pulling it towards you (A-B)
- Undo the fixing screws (D) of the shell.
- Move the housing base forwards and then upwards to unhook it
from the frame
- Lift the control panel and successively turn it forward
- Undo by two turns the screw of the pressure test point upstream
from the gas valve and connect the pressure gauge
- Power the boiler electrically by setting the main system switch to
“ON”
D
C
A
B
- Generate a heat demand via the ambient thermostat
- With the burner at maximum output, check that the gas pressure is
comprised between the minimum and rated power supply pressure
values indicated in the table
- Interrupt the heat demand
- Disconnect the pressure gauge and tighten the pressure test point
screw again upstream from the gas valve.
Pressure test point
upstream of the valve
DESCRIPTION
METHANE
GAS
(G20)
LIQUID
PROPANE
GAS (G31)
Lower Wobbe index
(at 15°C-1013 mbar)
45.67
70.69
MJ/
m
3
S
Supply nominal pressure
20
37
mbar
Supply minimum pressure
10
-
mbar
FAMILY CONDENS 2.5 IS E
Diameter of the main
burner nozzles
63
63
mm
Burner length
95
95
mm
Number of diaphragm holes
2
2
nr
Diaphragm holes diameter
1x4,70 flap +
1x4,20 free
1x3,40 flap+
1x3,25 free
mm
FAMILY CONDENS 3.0 IS E
Diameter of the main
burner nozzles
63
63
mm
Burner length
110
110
mm
Number of diaphragm holes
2
2
nr
Diaphragm holes diameter
1x4,30 flap +
1x4,20 free
1x3,40 flap +
1x3,25 free
mm
FAMILY CONDENS 3.5 IS E
Diameter of the main
burner nozzles
63
63
mm
Burner length
120
120
mm
Number of diaphragm holes
2
2
nr
Diaphragm holes diameter
1x5,1 flap +
1x4,7 free
2x3,55
mm
Combustion check
- Set the combustion analysis password.
- Insert the analyser probes in the prescribed positions on the air
box after removing the screws B and the cap C.
The flue gas analysis probe must be fully inserted as far as
possible.
- Tighten the analyser sealing screw in the flue gas analysis inlet
hole.
- The first display will show the number of rotations corresponding
to the maximum heating output, at which the boiler has been set
(see section "Adjustments" item P23). A subsequent rotation of the
encoder A turns on the boiler for the combustion control.
- Perform the combustion check.
- If the boiler needs to be calibrated, refer to section “Adjustments”.
- Remove the analyser probe and close the combustion analysis
inlet.
- Close the instrument panel and reassemble the cover in the re-
verse order compared to the disassembly description.
Even during the combustion analysis phase, the function that
switches the boiler off when the water temperature reaches the
maximum limit (about 90°C) remains enabled.
When the checks are completed:
- Press the
key to select the type of operation.
Summary of Contents for FAMILY CONDENS 2.5
Page 3: ...FAMILY CONDENS IS E 3...
Page 68: ...FAMILY CONDENS IS E 68 M R AF G AC 9 11...
Page 70: ...FAMILY CONDENS IS E 70 A C B D 1 2 3 4 5 7 9 11 12 13 10 F E 6 8 14 15...
Page 86: ...FAMILY CONDENS IS E 86 fig 29 fig 32 fig 31 fig 30 B A C D...
Page 87: ......
Page 88: ...Cod 20120920 05 16 Ed 0...