FAMILY CONDENS IS E
22
ADJUSTING THE MINIMUM OUTPUT (P. LL)
- Select parameter LL (with the boiler OFF) and wait until the boiler
ignites.
- Check the minimum CO
2
value shown on the flue gas analyser
(see "combustion check") corresponds to the values shown in
table 4.
If the CO
2
is different from the values shown in the table, turn the
minimum output adjustment screw (clockwise to increase the value)
with a screwdriver until the value shown in table 4 is indicated.
TABLE 4
Min. CO
2
METHANE
GAS (G20)
LIQUID
PROPANE
GAS (G31)
2.5 IS E
9.0
10.0
%
3.0 IS E
9.0
10.0
%
3.5 IS E
9.0
10.0
%
POSSIBILITY OF ADJUSTING THE HEATING MAXIMUM (P. 23) -
RANGE RATED
- Select parameter 23.
- Press the ENTER key to be able to modify the parameter value.
- Turn the encoder to modify the maximum fan speed (table 5).
- Confirm the new value by pressing ENTER.
The newly set value must be indicated on the adhesive label (sup-
plied) and will become the reference for subsequent checks and ad-
justments, including combustion checks.
TABLE 5
MAXIMUM NUMBER
OF FAN ROTATIONS
return fault
METHANE
GAS (G20)
LIQUID
PROPANE
GAS (G31)
2.5 IS E
45
45
rpm
3.0 IS E
51
49
rpm
3.5 IS E
53
54
rpm
POSSIBILITY OF ADJUSTING THE HEATING MINIMUM (P. 24)
- Select parameter 24.
- Press the ENTER key to be able to modify the parameter value
- Turn the encoder to modify the minimum fan speed.
- Confirm the new value by pressing ENTER.
Exit the CALIBRATION & SERVICE functions by pressing the ES
-
CAPE key.
The boiler switches off and ENERGY FOR LIFE is displayed.
Disconnect the pressure gauge and re-tighten the pressure test point
screw.
To restore operation, press the
key.
After each intervention on the adjustment element of the gas
valve, seal it with sealing varnish.
A power failure during the adjustment phase causes the non-in-
troduction of the modified parameters in the memory, which is
indicated by fault 54 on start-up.
Reprogram all the parameters you want to change.
The boiler is supplied with the adjustments shown in the table. De-
pending on plant engineering requirements or regional flue gas emis-
sion limits it is, however, possible to modify this value, referring to the
graphs below.
Summary of Contents for FAMILY CONDENS 2.5
Page 3: ...FAMILY CONDENS IS E 3...
Page 68: ...FAMILY CONDENS IS E 68 M R AF G AC 9 11...
Page 70: ...FAMILY CONDENS IS E 70 A C B D 1 2 3 4 5 7 9 11 12 13 10 F E 6 8 14 15...
Page 86: ...FAMILY CONDENS IS E 86 fig 29 fig 32 fig 31 fig 30 B A C D...
Page 87: ......
Page 88: ...Cod 20120920 05 16 Ed 0...