61
SHUTDOWN
61
APPENDIX
Menu item
Sub item / Parameter
Range
Default Value
Units
User level
(80) Max Setp Offset Up
0…40
5
°C
2: Installer
(81) Start Mod Delay Fact
0…60
60
Min.
2: Installer
(82) Next Module Start Rate
10…100
80
%
2: Installer
(83) Next Module Stop Rate
10…100
25
%
2: Installer
(84) Module Rotation Interval
0…30
1
Days
2: Installer
(149) First Module to Start
1…16
1
2: Installer
(86) MC PID P
0…1275
50
3: Factory
(87) MC PID I
0…1275
500
3: Factory
(150) MC PID Slew Rate Up
0…25.5
1.0
3: Factory
(151) MC PID Slew Rate Dn
0…25.5
1.0
3: Factory
(152) PwrMode2 Min Power
0…100
20
%
2: Installer
(153) PwrMode2 Hysteresis
0…100
40
%
2: Installer
(154) Post-Pump period
0…255
60
Sec.
2: Installer
(184) N. active burner for DHW
0…16
16
2:Installer
Boiler Cascade Settings
(73) Boiler Address
Stand-alone (0)
Managing (1)
Dependent (2...8)
Stand-alone
2: Installer
(156) Permit Emergency Mode
Yes/No
Yes
1: User
(157) Emergency Setpoint
20…90
70
°C
2: Installer
(158) Delay Per Start Next Blr.
0…1275
1275
Sec.
2: Installer
(159) Delay Per Stop Next Blr.
0…1275
1275
Sec.
2: Installer
(160) Delay Quick Start Next
0…1275
400
Sec.
2: Installer
(161) Delay Quick Stop Next
0…1275
240
Sec.
2: Installer
(162) Hyst Down Start Boiler
0…40
5
°C
2: Installer
(163) Hyst Up Stop Boiler
0…40
2
°C
2: Installer
(164) Hyst Down Quick Start
0…40
10
°C
2: Installer
(165) Hyst Up Quick Stop
0…40
4
°C
2: Installer
(166) Hyst Up Stop All
0…60
8
°C
2: Installer
(167) Number of boilers
1…16 (basic cascade) 1…8
(full cascade)
1
2: Installer
(168) Power Mode
0) Disabled
2) Max burners
3) Balanced burners
2
2: Installer
(169) Max. Setp. Offset Down
0…40
2
°C
2: Installer
(170) Max Setp Offset Up
0…40
5
°C
2: Installer
(171) Start Mod Delay Fact
0…60
40
Min.
2: Installer
(172) Next Boiler Start Rate
10…100
80
%
2: Installer
(173) Next Boiler Stop Rate
10…100
25
%
2: Installer
(174) Boiler Rotation Interval
0…30
5
Days
2: Installer
(175) First Boiler to Start
1…8
-
2: Installer
(176) BC PID P
0…1275
25
3: Factory
(177) BC PID I
0…1275
1000
3: Factory
(178) BC PID Slew Rate Up
0…25.5
1.0
3: Factory
(179) BC PID Slew Rate Dn
0…25.5
1.0
3: Factory
(180) PwrMode2 Min Power
0…100
20
%
2: Installer
(181) PwrMode2 Hysteresis
0…100
40
%
2: Installer
(182) Post-Pump period
0…255
30
sec
2: Installer
Summary of Contents for Array AR 3000
Page 1: ...cod Doc 0079789 rev 5 09 2018 Array AR 3000 AR 4000 US INSTALLATION AND OPERATION MANUAL...
Page 39: ...39 SHUTDOWN 39 APPENDIX WIRING DIAGRAM DEPENDENT 5 6 7 8 RIGHT DOOR...
Page 69: ...69...
Page 70: ...70...
Page 71: ...71...