16
INSTALLATION
4.6
Water Quality Guidelines
Excessive water hardness causing a lime buildup in the stainless
steel coils or tubes is not a fault of the appliance and is not covered
by warranty. Water hardness must fall within the following limits:
Parameters
Units
Value
General feature -
Colorless, no sediment
PH value
PH
Min 6.5; Max 9
Dissolved Oxygen
mg/l
< 0.05
Total iron (Fe)
mg/l
< 0.3
Total copper (Cu)
mg/l
< 0.1
Na
2
SO
3
mg/l
< 10
N
2
H
4
mg/l
< 3
PO
4
mg/l
< 15
CaCO
3
ppm
Min 50 ; Max 150
Trisodium Phosphate ppm
absent
Chlorine
ppm
< 100
Pressure
PSI
Min 7.25; Max 80
Glycol
%
Max 40% (only propylene glycol)
− Avoid an automatic water fill system.
− Use only untreated water to fill the system.
− Do not use TSP (tri-sodium phosphate)
− Do not use fill water treated with salt bedding type
exchangers (ion exchanger).
− Consult a local water treatment specialist for
recommendations if any of the above table is outside the
stated ranges.
− When using oxygen permeable PEX, the system must be
separated from the boiler by a heat exchanger.
− A correctly sized and working expansion vessel must be
installed.
− Excessive flow can cause erosion damage to the heat
exchanger.
9
CAUTION:
For freeze protection use only propylene glycol, with
scale inhibitors, with a maximum concentration (by volume)
of 50% glycol. Frost protection and inhibitor level has to be
checked annually during the regular scheduled maintenance
of the condensing boiler.
9
CAUTION:
The boiler, when used in connection with a
refrigeration system, must be installed so the chilled medium
is piped in parallel with the boiler with appropriate valves to
prevent the chilled medium from entering the boiler.
9
CAUTION:
The boiler piping system of a hot water boiler
connected to heating coils located in air handling units where
they may be exposed to refrigerated air circulation must be
equipped with flow control valves or other automatic means
to prevent gravity circulation of the boiler water during the
cooling cycle. A minimum water pressure is required for
optimum performance. Minimum water pressure required:
7.25 psi (0.5 bar).
4.7
Supply and Return Piping
The
Array
Boiler utilizes 4” flanges, for both models
AR 3000
and
AR 4000,
for the water system supply and return piping
connections. The physical location of the supply and return piping
connections is on the top of the unit as shown in Fig. 9.
Water
Return
(Inlet)
Gas
connection
Water
Supply
(Outlet)
Fig. 9
Array AR 3000 and AR 4000 Connections
9
CAUTION:
Before connecting the boiler to the heating system,
flush the heating system to remove sediment, flux, dirt, and
other foreign matter. The heat exchanger may be damaged by
sediment or corrosion.
9
CAUTION:
Do not use cleaning fluids that are not compatible
with the boiler materials, including acids (e.g. hydrochloric
acid and/or similar ones) at any concentration.
9
CAUTION:
Introducing fresh water to the system increases
the oxygen presence and can cause corrosion of metallic
components. Immediately repair any drips or leaks in the
system to avoid constant introduction of air into the system.
9
CAUTION:
Excessive fluctuation in pressure changes in the
system can cause fatigue and stress on the heat exchanger.
This is detrimental to the integrity of the boiler and system
components, it is mandatory to maintain a constant operating
pressure.
A minimum water pressure is required for optimum performance.
Minimum water pressure required: 7.25 psi (0.5 bar).
4.8
Low Water Cutoff
A low water protection is installed at two levels:
− boiler level
− heat exchanger level
Boiler level:
a Low Water Cut Off (LWCO) sensor is installed on top of the supply
header of each boiler. To check its functionality, go to the HMI
touchscreen, access the Boiler screen (see section 6.3.3), push
LWCO TEST button and confirm. On the screen will appear the error
Summary of Contents for Array AR 3000
Page 1: ...cod Doc 0079789 rev 5 09 2018 Array AR 3000 AR 4000 US INSTALLATION AND OPERATION MANUAL...
Page 39: ...39 SHUTDOWN 39 APPENDIX WIRING DIAGRAM DEPENDENT 5 6 7 8 RIGHT DOOR...
Page 69: ...69...
Page 70: ...70...
Page 71: ...71...