APPENDIX K - LIST OF PARAMETERS (WITH RANGES AND DEFAULT VALUES)
Menu item
Sub item / Parameter
Range
Default Value
Units
User level
Boiler Parameters
(1) CH Mode
0…5
0
2: Installer
(3) CH Setpoint
30…90
70
°C
1: User
(185) Calc. Setp. Offset
-10…10
0
°C
2: Installer
(109) MN Climate Curve Comp
-10…10
0
°C
2: Installer
(110) CH Min Setpoint
20…50
30
°C
2: Installer
(111) CH Max Setpoint
50…90
80
°C
2: Installer
(5) Boiler Pump Overrun
0…900
60
Sec.
2: Installer
(6) Flue Temp Limit
10…120
100
°C
3: Factory
(7) CH Hysteresis Up
0…20
5
°C
2: Installer
(112) CH Hysteresis Down
0…20
5
°C
2: Installer
(9) Anti Cycle Period
10…900
120
Sec.
2: Installer
(10) Anti Cycle Temp Diff
0…20
16
°C
2: Installer
(12) Hx Diff
Δ
T Maximum
10…60
40
°C
3: Factory
(13) Hx Diff Max Wait Time
10…250
30
Sec.
3: Factory
(14) Max Power CH
50…100
100
%
2: Installer
(15) Min Power CH
1…30
1
%
2: Installer
(16) CH PID P
0…1275
100
3: Factory
(17) CH PID I
0…1275
250
3: Factory
(18) CH PID D
0…1275
0
3: Factory
(19) Design Supply Temp
30…90
80
°C
1: User
(20) Design Outdoor Temp
-25…25
0
°C
1: User
(21) Baseline Supply Temp
30…90
40
°C
2: Installer
(22) Baseline Outdoor Temp
0…30
20
°C
2: Installer
(23) Design Supply Min Limit.
4…82
30
°C
2: Installer
(24) Design Supply Max Limit
27…90
80
°C
2: Installer
(25) Warm Weather Shutdown
0…35
22
°C
2: Installer
(26) Boost Temp. Increment
0…30
0
°C
2: Installer
(27) Boost Time Delay
1…120
20
Min.
2: Installer
(28) Night Setback Temp.
0…30
10
°C
2: Installer
(35) DHW Mode
0) Disabled
1) Tank + sensor
2) Tank + thermostat
0
2: Installer
(113) Max Power DHW
50…100
100
%
2: Installer
(114) Min Power DHW
1…30
1
%
2: Installer
(36) DHW Tank Hyst Down
0…20
5
°C
2: Installer
(37) DHW Tank Hyst Up
0…20
5
°C
2: Installer
(38) DHW Tank Supply Extra
0…30
15
°C
2: Installer
(39) DHW Tank Supp Hyst Dn
0…20
5
°C
3: Factory
(40) DHW Tank Supp Hyst_Up
0…20
5
°C
3: Factory
(41) DHW Tank Hold Warm
0…10
5
°C
3: Factory
(42) DHW Priority
On (DHW), Off (CH), Time
On
2: Installer
(43) DHW Max Priority Time
1…255
30
Min.
2: Installer
(44) DHW Pump Overrun
0…900
60
Sec.
2: Installer
(45) DHW Tank PID P
0…1255
100
3: Factory
(46) DHW Tank PID I
0…1255
500
3: Factory
(47) DHW Tank PID D
0…1255
0
3: Factory
(48) DHW/Tank Setpoint
40…71
50
°C
1: User
(115) DHW Store Setpoint
40…71
57
°C
1: User
(49) DHW Hysteresis Down
0…20
4
°C
3: Factory
(50) DHW Hysteresis Up
0…20
4
°C
3: Factory
(51) DHW Instant PID P
0…1255
100
3: Factory