29
COMMISSIONING
Adjusting the parameters on that screen, the reset curve below
will modify shape and slope to meet the needs of the specific
application.
20
OUTDOOR TEMP. (°C/°F)
Reset Curve
Design Boiler
93
Reset Curve
Outdoor Design
1) Reset Curve Outdoor Mild Weather
2) Warm Weather Shutdown
Reset Cuve
Boiler Mild
Weather
Reset Curve Boiler
Maximum
200
82 180
71 160
60 140
120
49
100
38
27 80
60
16
°C °F
-6
40
4
60
16
80
27
100
38
°F
°C
Reset Curve Boiler
Minimum
CH SETPOINT (°C/°F)
Fig. 41
Reset Curve
− The boiler will fire only when there is a call for heat and
the heating temperature setpoint is higher than the actual
supply temperature. Hold buttons “+” or “-“ on the Cascade
screen (Fig. 48) to select the desired heating temperature. If
the external temperature sensor is connected (connected,
see Section “4.14.3 Outdoor Temperature Sensor” page”4.14.3
Outdoor Temperature Sensor” page 23)
− The boiler CH setpoint can be controlled by an analog input
signal provided by a remote means such as a Building
Management System or a system controller. The analog
input 0-10 VDC, is used to adjust the boiler setpoint between
the CH_Setpoint_Min and the CH_Setpoint_Max settings
(Figure 35). To enable this operation mode, the parameter
CH mode must be set to 4 (see
Array
Control System Manual
for accessing the parameter list).
Fan Speed
Maximum
Fan Speed
Minimum
1.5
1.0
2.0
9
Voltage
OFF
ON
ON/OFF
Hysterese
OFF
ON
Modulating
Fig. 42
10VDC Control mode
The CH setpoint Min and CH setpoint Max parameters can be
adjusted to provide the desired temperature adjustment band. A
heat request will be generated by an input of 1.5 volts or higher.
The setpoint modulation will occur between 2 and 10 volts. The
request for heat will be removed when the voltage drops below
1 volt.
All other safety and control functions associated with the boiler
will react normally to adverse condition and override control of the
analog signal to prevent an error condition.
5.5.1
Minimum Water Flow (Heat Exchanger
Protection)
This unit is self-protected against low water flow. A flow meter
continuously monitors the water flow to each module. If the
water flow decreases below the minimum stated, the burner
automatically shuts off.
5.5.2
Heating System Pressure Test
If the pressure inside the heating circuit falls below the minimum
pressure for the system (7.5 PSI), the appliance switches off and
the 905PB inner display shows “Low water pressure” to indicate
that it is necessary to restore the correct pressure.
Open the filling valve and check the pressure on the temperature/
pressure gauge of Fig. 43.
The error will disappear when the pressure is back at the correct
value. To prevent accidental relief valve openings, fill the heating
circuit slowly.
Temperature/Pressure
Gauges
Fig. 43
Temperature/Pressure Gauge location