60
SHUTDOWN
60
APPENDIX
Menu item
Sub item / Parameter
Range
Default Value
Units
User level
(187) Prog. Output 5.
0) Disabled
1) General Pump
2) CH Pump
3) DHW Pump
4) System Pump
5) Cascade Pump
6) Alarm Relay
7) Filling Valve
8) LPG Tank
9) External Igniter
10) Air Damper
14) Alarm Burner CC
15) Status Burner CC
16)Zone pump
17)Mixing valve open
18)Mixing valve closed
19)Anti-legionella pump
*See Appliance
settings
2: Installer
(129) Flow Sensor
Bitron, Huba: DN8, DN10,
DN15, DN15, DN20, DN25
Huba DN25
2: Installer
(130) Flow Scaling Factor
0…25.5
3.2
rpm/l
2: Installer
(131) Min Pressure
Off, 0.3…5.0
0.1
bar
2: Installer
(132) Pressure Fill Hyst.
0.2…5.0
0.5
bar
2: Installer
(133) Mod. Pump dT
5…40
15
°C
2: Installer
(134) Mod. Pump Start Time
0…255
120
Sec.
2: Installer
(135) Mod. Pump Type
0. Wilo Yonos
1. Salmson
2. Grundfos
Grundfos
2: Installer
(136) Mod. Pump Mode
0. On/Off
1. Modulating
2-10 Fixed 20… 100%
Modulating
2: Installer
(137) Mod. Pump Min Power
0…100
30
%
2: Installer
(138) Appliance Type
50…55
50
2: Installer
(139) Dair active
Yes, No
No
2: Installer
(140) Minimal Flow
0.0…100
17
l/min
2: Installer
(107) Anti-legionella Day
Sun…Sat.
Sun
Day
2: Installer
(108) Anti-legionella Hour
0…23
0
Hour
2: Installer
(183) High Limit Test
Simulated/Physical
Simulated
3: Factory
(205) Dep. Zone Control
Disabled/Enabled
Disabled
1: User
(155) Frost Protection
10…30
15
°C
2: Installer
(186) Frost protection outdoor
-30...15
5
°C
2:Installer
Module Cascade Settings
(72) Permit Emergency Mode
Yes/No
Yes
1: User
(74) Emergency Setpoint
20…90
70
°C
2: Installer
(75) Delay Per Start Next Dep
5…255
120
Sec.
2: Installer
(76) Delay Per Stop Next Dep
5…255
30
Sec.
2: Installer
(142) Delay Quick Start Next
5…255
60
Sec.
2: Installer
(143) Delay Per Quick Stop Next
5…255
15
Sec.
2: Installer
(77) Hyst Down Start Module
0…40
5
°C
2: Installer
(78) Hyst Up Stop Module
0…40
4
°C
2: Installer
(144) Hyst Down Quick Start
0…40
20
°C
2: Installer
(145) Hyst Up Quick Stop
0…40
6
°C
2: Installer
(146) Hyst Up Stop All
0…40
8
°C
2: Installer
(147) Number of Units
1…16 (basic cascade) 1…8
(full cascade)
8
2: Installer
(148) Power Mode
0) Disabled
1) Min burners
2) Max burners
3) Balanced burners
2
2: Installer
(79) Max. Setp. Offset Down
0…40
2
°C
2: Installer