58
SHUTDOWN
58
APPENDIX
Menu item
Sub item / Parameter
Range
Default Value
Units
User level
(52) DHW Instant PID I
0…1255
160
3: Factory
(53) DHW Instant PID D
0…1255
0
3: Factory
(60) Flow Rate Start
0.1…20
1.4
l/min
3: Factory
(61) Flow Rate Lo Temp Pwr
0.1…20
1.4
l/min
3: Factory
(62) Flow Rate Hi Temp Pwr
0.1…20
1.4
l/min
3: Factory
(63) DHW On Off Period
10…60
30
Sec.
3: Factory
(64) PreHeat Mode
Off, Comfort, Eco, Anti-Fr
Off
1: User
(65) PreHeat Eco Setpoint
20…60
30
°C
3: Factory
(67) PreHeat After Tap Hld Time
0…255
30
Sec.
3: Factory
(68) After Tap Hold Time
0…255
120
Sec.
3: Factory
(69) PreHeat Hyst Down
0…30
5
°C
3: Factory
(70) PreHeat Hyst Up
0…30
0
°C
3: Factory
(71) PreHeat Delay Time
0…15
10
Sec.
3: Factory
(92) Fan Speed Maximum
0…12750
*See Appliance
settings
RPM
2: Installer
(93) Fan Speed Minimum
0…12750
*See Appliance
settings
RPM
2: Installer
(94) Fan Speed Ignition
0…12750
*See Appliance
settings
RPM
2: Installer
(116) Prog. Input 1.
0) Disabled
1) Water pressure sensor
2) CH flow switch
3) Flue pressure switch
*See Appliance
settings
2: Installer
(117) Prog. Input 2.
0) Disabled
1) DHW flow sensor
2) DHW flow switch
3) CH flow sensor
*See Appliance
settings
2: Installer
(118) Prog. Input 3.
0) Disabled
1) Drain switch
2) Gas pressure switch
*See Appliance
settings
2: Installer
(119) Prog. Input 4.
0) Supply 2 sensor
1) Disabled
2) Air Damper Switch
*See Appliance
settings
2: Installer
(120) Prog. Input 5.
0) Disabled
1) T_Return sensor
2) Extern switch
*See Appliance
settings
2: Installer
(121) Prog. Input 6.
0) Disabled
1) T_Flue sensor
2) Flue switch
3) APS switch
*See Appliance
settings
2: Installer
(122) Prog. Input 7.
0) Disabled
1) T_Flue_2 sensor
2) T_ Bl. Flue
3) T_System sensor
4) Blocked Flue switch
5) Cascade Sensor
*See Appliance
settings
2: Installer
(123) Prog. Input 8.
0) Disabled
1) T_DCW sensor
2) Water pressure switch
*See Appliance
settings
2: Installer
(124) Prog. Input RT.
0) Disabled
1) Enabled
1
2: Installer
Summary of Contents for Array AR 3000
Page 1: ...cod Doc 0079789 rev 5 09 2018 Array AR 3000 AR 4000 US INSTALLATION AND OPERATION MANUAL...
Page 39: ...39 SHUTDOWN 39 APPENDIX WIRING DIAGRAM DEPENDENT 5 6 7 8 RIGHT DOOR...
Page 69: ...69...
Page 70: ...70...
Page 71: ...71...