Faults - Possible causes - Solutions
608
1 *1)
1 *1)
Invalid drop of the boiler safety interlock chain
609
1 *1)
1 *1)
Invalid drop of the gas safety interlock chain
610
Optional
*1)
3 *1)
Invalid drop of the oil safety interlock chain
611
Optional
3
Gas pressure too low
613
0
0
Air pressure signal is missing
617
1
1
Flame signal extinguishes during operation
624
Optional
3
Oil pressure too low
711
0
0
Invalid change of the operation mode
713
0
0
Invalid signal combination in operating mode BURNER OFF
714
0
0
Invalid signal combination in operating mode BURNER READY
715
0
0
Invalid signal combination in operating mode PRE-PURGE
716
0
0
Invalid signal combination in operating mode IGNITION POSITION
717
0
0
Invalid signal combination in operating mode IGNITION
719
0
0
Fuel valves are open for too long without a flame
720
0
0
Ignition transformer activated too long
721
0
0
Ignition valve openes for too long
722
0
0
Fuel valves open in maintenance mode
723
0
0
Ignition process needs too much time
724
0
0
Gas valve open with fuel oil
725
0
0
Oil valves are open while gas is selected
727
0
0
Main gas 1 opens unexpectedly
728
0
0
All three gas valves open for too long
729
0
0
Ignition process lasts for too long (without pilot burner)
730
0
0
Maintenance mode without pilot burner
731
0
0
Ignition valve opens without pilot burner
732
0
0
Invalid signal combination at input terminals during operation
734
0
0
Pre-ventilation period not respected
739
0
0
Leakage test: main gas valve 2 opens for too long
740
0
0
Leakage test: main gas valve 1 leaky
741
0
0
Leakage test: main gas valve 1 opens for too long
742
0
0
Leakage test: main gas valve 2 leaky
743
0
0
Flame monitoring: flame burns for too long after shutdown
745
0
0
Program monitoring time exceeded
746
0
0
Solenoid valve cannot be switched off
747
0
0
Leakage test: Venting into the burner is not allowed
759
0
0
BT300 leaves SETTING mode automatically after 24 hours
763
0
0
Different curve selection on main processor and watchdog proces-
sor
764
1
1
CO-controller - internal curve set failure
Curve set
800
0
0
Parameter defective
Parameter
No.
801
0
0
Channel control mode is inconsistent between main processor and
watchdog processor (fatal error, no automatic restart possible)
Channel
802
1
1
Integration of a channel into the fuel/air ratio control takes too long
(only one automatic restart possible)
Channel
803
0
0
Channel is out of 1
st
monitoring band for too long
Channel
804
0
0
Channel mode of the fuel/air ratio control does not match to the ac-
tivation type
Channel
805
0
0
Directly controlled channel runs to an invalid position, i.e. a channel
that is not deactivated or controlled by fuel/air ratio control
C
set point
position
Fault code
TRD
P301=0
P328>0
EN67
P301=2
P328>0
Description
D1
D2
Summary of Contents for 20155654
Page 2: ...Original instructions...
Page 73: ...71 20155699 GB Appendix Electrical panel layout RS 310 410 E FGR...
Page 74: ...20155699 72 GB Appendix Electrical panel layout RS 510 610 E FGR...
Page 75: ...73 20155699 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Page 76: ...20155699 74 GB Appendix Electrical panel layout...
Page 77: ...75 20155699 GB Appendix Electrical panel layout 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Page 78: ...20155699 76 GB Appendix Electrical panel layout 0 0 0 1 1 23 4567 23 4567...