Technical description of the burner
4.13
Burner operating sequence
Tab. H
Key to layout (Fig. 8)
FGR
FGR release
X01
Gas valve 1
X02
Gas valve 2
X03
Pilot valve
X04
Ignition transformer
X05
Gas pressure > min.
X06
Gas safety circuit
X07
Boiler safety circuit
X08
Air pressure switch
X10
Burner ON
X20+X21 Flame signal
X24
Fault
X25
Fan ON
X32
Air servomotor
X33
Fuel servomotor
X34
FGR servomotor
Fig. 8
X07
X06
X10
X05
X08
X20+X21
FGR
X32
X33
X34
X04
X03
X01
X02
X25
X24
S9612
Any condition
t1
Waiting time for safety circuits consent
(boiler fuel)
t2
Opening time of the gas valve (with
sealing control active)
2.4 s
t3
Servomotor opening time
30/60 s
t4
Activation time FGR servomotor
0 - t5
t5
Pre-purge time
adjustable
t6
Pre-ignition time
adjustable
t7
Ignition flame safety time
3 s
t8
Flame stabilization time
adjustable
t9’
Safety time 2
nd
stage
3 s
t10
Modulation phase
t11
Adjustment time
t12
Opening time of the gas valve (with
sealing control active)
3 s
t13
Post-purge time
adjustable
t15
Post-combustion time
adjustable
t16
Checking time for flame extinction
5 s
t17
Checking time for gas valve (with seal-
ing control active)
30 s
Summary of Contents for 20155654
Page 2: ...Original instructions...
Page 73: ...71 20155699 GB Appendix Electrical panel layout RS 310 410 E FGR...
Page 74: ...20155699 72 GB Appendix Electrical panel layout RS 510 610 E FGR...
Page 75: ...73 20155699 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Page 76: ...20155699 74 GB Appendix Electrical panel layout...
Page 77: ...75 20155699 GB Appendix Electrical panel layout 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Page 78: ...20155699 76 GB Appendix Electrical panel layout 0 0 0 1 1 23 4567 23 4567...