Operating control and display
Use cursor keys
to set firing rate point and press EN-
TER
to confirm.
Set-point channel 1 is chosen (displayed inversely).
Use cursor keys
to set channels' actuator position.
Use cursor keys
to switch to next channel.
Use cursor keys
to set actuators' position in the select-
ed firing rate point.
NOTE:
Actuators move according to changes immediately to the
set position.
If you want to change channel 4 the fan motor must be run-
ning.
Accept or discard the entry!
The display switches to the firing rate selection menu.
Use BACK key
to switch to menu settings after having com-
pleted curve settings.
NOTE:
the following firing rate points are available: ignition point
, 200, 250, 300, 400, 500, 600, 700, 800, 900, 999.
Set your firing rate points as described above and press ENTER
to confirm
.
NOTE:
if you press key
while setting firing rate points your val-
ue changes will be discarded.
Set multi-stage oil operation - 1st stage
1
Display 1st stage
2
Set-point, air damper position
3
Actual value, air damper position
Select the first stage and press ENTER
.
The actuators move to the pre-set positions.
The set-point position of the first activated actuator is displayed
inversely.
Use cursor keys
to set the position of the selected ac-
tuator.
Use cursor keys
to switch to a different actuator.
Press ENTER
.
The positions of all actuators of the selected firing rate point are
saved.
You can select the next firing rate point.
NOTE:
if you press the key
while changing the firing rate point
your changes will be discarded.
NOTE:
During multi-stage operation, the following points are avail-
able:
Ignition point
:
1 (first stage)
1
→
2 (valve switch-on point, second stage)
1
←
2 (valve switch-off point, second stage)
2 (second level)
2
→
3 (valve switch-on point, third stage)
2
←
3 (valve switch-off point, third stage),
3 (third stage)
NOTE:
pre-purge starts as soon as the damper reaches pre-purge
position and - if you use a VSM - the last but one point of the
fuel/air ratio curve is passed.
The points are approached from above by using the over-
shoot-function. If you use the over- shoot-function in opera-
tion, you must program all points from above. Only if you do
so, the required position will match the actual position.
The channels' position in the last but one curve point must
be lower than at the last curve point.
Fig. 72
S9411
Fig. 73
S9618
X03
X02
X01
Air servomotor
1st stage 2nd stage 3rd stage
Firing rate
Oil valve
Oil
Summary of Contents for 20155654
Page 2: ...Original instructions...
Page 73: ...71 20155699 GB Appendix Electrical panel layout RS 310 410 E FGR...
Page 74: ...20155699 72 GB Appendix Electrical panel layout RS 510 610 E FGR...
Page 75: ...73 20155699 GB Appendix Electrical panel layout 01 2 3 4506 7 891 01...
Page 76: ...20155699 74 GB Appendix Electrical panel layout...
Page 77: ...75 20155699 GB Appendix Electrical panel layout 0 0 0 1 1 1 2 1 3 1 1 1 1 1 1 1 41 4 4 1 1 2 1...
Page 78: ...20155699 76 GB Appendix Electrical panel layout 0 0 0 1 1 23 4567 23 4567...