If the safety strip is engaged (NO contact), the movement is allowed only
with man present (see section
FUNCTIONING IN DEAD MAN MODE
WHEN THE SAFETY DEVICES ARE FAILING
).
In case the safety strip is not installed, this contact must be short
circuited with a wire jump (from EDGE to COM) to permit the shutter
to operate.
PAY ATTENTION:
it is highly recommended to check safety-strips
operation at least every 6 months.
SAFETY STRIP ALLARM
If after the first safety strip obstacle detection, the safety strip is released
and then engaged again before the end of the shutter travelling, the
shutter interrupts any movement and this
alarm state
will be signalled
by the Blinker or by the courtesy light for 1 minute together with DL1
programming light that will blink every 4 seconds. The normal shutter
operations can be restored by pressing any push button or radio
commands.
TESTING THE SAFETY STRIP equipment (DIP7 ON)
The DIP7 ON enables the Test of safety strip equipment. The Test is
performed every time the shutter completes a full opening. It is suitable
only if the safety strip device is equipped with a dedicated power supply
input.
In fact, the safety strip equipment power supply input has to be connected
to the A+TEST and A- outputs (DIP7 ON). Automatically, every time the
shutter completes a full opening, just before closing, the control board
switches OFF the A+TEST and A- power supply output for a very short
time. While the safety strip power supply is switched OFF, if everything is
working fine the safety strip contact (EDGE - COM) must open. In case
the test fails, no other gate manoeuvre will be allowed and the alarm state
will be signalled by the blinker or by the courtesy light that will remain on.
NOT ALL THE SAFETY STRIPS CAN BE TESTED, THUS THE SWITCH
DIP7 MUST BE LEFT OFF.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES
ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or
if photocell fails or remain engaded for more than 60 seconds, the K
BUTTON command will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of
the programming led.
With the blinking of the programming led, the opening and closing
operation are allowed only with the command button pressed and held.
The radio commands and that of automatic closing, will be excluded,
since their use in this mode, is not allowed by the norms.
Once the failing safety device is repaired, in automatic after 1 second, all
standard commands that were selected, such as step by step, automatic
mode, radio commands and automatic closing start functioning again.
Note 1:
during this functioning in dead man mode, in case of damage to
the safety strips (or photocells) the photocells (or safety strips)
still work by interrupting the operation in progress.
The dead-man operation is only an emergency operation which
must be activated for a very short period and with the complete
installation at sight so to have a secure and safe control of the
system. As soon as possible however, the failing safety devices
must be repaired and activated.
BLINKER AND/OR FLASHING LIGHT (DIP5)
With DIP5 set ON =>
it is possible to connect a flasher
N.B.: This electric board can supply power
ONLY TO BLINKERS WITH (ACG7059)
BLINKING CIRCUIT, with max. 40W
lamps.
With DIP5 set OFF =>
it is possible to connect a lamp for garage lighting
(40 W max).
On every command input, the courtesy lamp will lit for 2 minutes. If during
the 2 minutes time, a second input is generated, the time elapsing will
automatically restart for 2 minutes.
PRE-FLASHING FUNCTION
With DIP8 set OFF =>
the FLASHING LIGHT and the motor will start at
the same time.
With DIP8 set ON =>
the FLASHING LIGHT starts working 3 seconds
before every movement of the motor.
AUTOMATIC CLOSING (DIP 3 ON)
The pausing time before the automatic closing is set during the “Time
Programming”.
In this case the maximum pausing time available is 5 minutes.
Pause time can be enabled or disabled by DIP3 (ON enabled).
RESTORING OF OPERATION FOLLOWING A POWER SHUT OFF
In case of power shut off the fence stops and the control unit will keep
memory of the interrupted motion. On restoring of power a further
command is necessary. Upon command input the interrupted operation is
completed (in case of opening, the open stroke is completed…).
T
ECHNICAL DATA
Temperature range
0±55°C
Moisture
<95% without condensation
Power supply voltage
230V±10% (120V±10% on
request)
Frequency
50/60Hz
Transient power mains drops
20ms
Max. power managed at the motor output 1CV
Max. load at the blinker output
40W with resistive load
Max. card power absorption (excluding the accessories)
20mA
Current available for the photocells
0,4A±15% 24Vdc
Protection degree
IP54
Weight of the equipment
0,70 kg
Dimensions
14,7 x 6 x 18,5cm
TECHNICAL FEATURES OF THE RADIO (CRX MODELS ONLY)
Frequency for the reception
433,92MHz
Impedance
52Ω
Sensitivity
>2,24µV
Energizing time
300ms
De-energizing time
300ms
Codes to be memorized
N° 60
Current available on the radio connector 200mA 12Vdc
- All inputs shall be used as clean contacts without earthing, because
the power supply is generated in the card and is structured in such a
way to guarantee the respect of double and reinforced insulation to the
elements under voltage
- All inputs are managed by a programmed circuit that carries out a self-
control every time the door is operated.