Example spaced U-Bolt locations.
All other U-Bolts to be fixed
Nuts/washers below the
bracket only for fixed joint.
Nuts/washers both sides of the bracket for
sliding joint.
Gap 3mm min.
5mm max
All the brackets on the burner tube, except,
the bracket adjacent to the U-Bend end,
should have spaced U-Bolts. All middle
brackets on the fan tube should have nuts
and washers on both sides of the bracket.
This is to allow the U-Bolt to be tightened
whilst still allowing a 3mm gap for the
tube to expand.
Slide the bracket assemblies along the tubes
to the correct position, in the correct order
(15-25kW models have a different first
bracket). Refer to detailed assembly draw-
ing (Figure 41 to Figure 50) for more details.
Note:
Do not tighten any of the nuts at this stage.
Models 15-25kW burner bracket and
models 30-50kW all brackets - M8
U-Bolt. Models 15-25kW remaining
brackets all M6 U-Bolts.
Example spaced U-Bolt locations.
All end U-Bolts to be fixed
Figure 26.3
U-Bolt to U-Tube heater suspension brackets
Figure 26.4
U-Bolt to U-Tube heater suspension brackets
Figure 26.5
U-Bolt to U-Tube heater suspension brackets
Fixed U-Bolt detail. Nut
and washers on bottom
of bracket.
Attach U-Bolts to the linear heater suspension
brackets.
Note:
U-Bolts, washers and nuts are stainless steel. All
other fixings are BZP.
Note that the 15-25kW linear heaters have
two types of U-Bolt, 30-50kW linear heaters
have one type of U-Bolt.
The bracket furthest from the burner must
be installed with the flange and reflector
fixing tabs facing away from the burner end
of the heater. All other brackets must have
the flanges facing towards the burner end.
Bracket furthest from burner has flange
facing away from burner end.
Looking
from above
the heater
Burner End
Bracket furthest from burner has flange
facing away from burner end.
Burner end bracket and all intermediate brackets
have flange facing towards burner end.
Spaced U-Bolt detail.
Nuts and washers both sides of bracket.
Fit nuts and washers to the U-Bolts and
loosely secure to the bracket.
All middle brackets should have the spaced
U-Bolt detail.
27
Summary of Contents for VS15LHE8
Page 34: ...A Figure 41 Vision Heater Assembly Models VSUTE VSUHE 15kW 76mm 3ins Nom Dia 34...
Page 35: ...A A Figure 42 Vision Heater Assembly Models VSUTE VSUHE 20 25kW 76mm 3ins Nom Dia 35...
Page 36: ...Figure 43 Vision Heater Assembly Models VSUTE VSUHE 30 35kW 100mm 4ins Nom Dia 36...
Page 37: ...Figure 44 Vision Heater Assembly Models VSUTE VSUHE 40kW 100mm 4ins Nom Dia 37...
Page 38: ...Figure 45 Vision Heater Assembly Models VSUTE VSUHE 45 50kW 100mm 4ins Nom Dia 38...
Page 39: ...A Figure 46 Vision Heater Assembly Models VSLIE VSLHE VSDLE 15 25kW 8m 76mm 3ins Nom Dia 39...
Page 40: ...A Figure 47 Vision Heater Assembly Models VSLIE VSLHE VSDLE 20 25kW 10 5m 76mm 3ins Nom Dia 40...
Page 41: ...Figure 48 Vision Heater Assembly Models VSLIE VSLHE VSDLE 30 35kW 10 5m 100mm 4ins Nom Dia 41...
Page 43: ...Figure 50 Vision Heater Assy Models VSLIE VSLHE VSDLE 35 40 45 50 kW 16m 100mm 4ins Nom Dia 43...
Page 59: ...Notes 59...