Figure 53.
Honeywell VK4105 Series
Figure 54.
SIT Sigma 840 Series
Gas inlet test point.
Injector pressure test point
Adjustment screw under-cap
to set injector pressure
Gas inlet test point.
Injector pressure test point
Adjustment screw under-cap to set
injector pressure
No
Yes
Check installation has
been carried out to these
instructions.
Ensure gas and electricity supplies
are isolated.
Disconnect gas hose from burner
Reconnect gas hose. Open
isolating valve. Check
soundness.
Open control housing and
check that all components,
are securely fastened.
Close control housing
Check thermostat is set to
maximum and is calling for heat.
Switch on electrical supply. The red
neon should now be illuminated.
If restarting heater a delay of 15s
should be allowed.
Open control housing and check that all
components are securely fastened. Ensure
vacuum at burner is greater than 80 Pa
The heater should now run through its
start up sequence and ignite.
A successful ignition is
indicated by the amber light
illuminating and remaining
illuminated.
Check gas pressure.
Check operation on flame failure.
Leave the instructions with a
responsible person.
Check operation of air
pressure switch
Close control housing
Replace burner on tube and secure.
Remove burner from tube and
inspect burner head.
(See servicing instructions)
Has the burner lit?
3.4 Gas valve adjustment
3.5 Commissioning chart for VS series unitary heaters
45
Summary of Contents for VS15LHE8
Page 34: ...A Figure 41 Vision Heater Assembly Models VSUTE VSUHE 15kW 76mm 3ins Nom Dia 34...
Page 35: ...A A Figure 42 Vision Heater Assembly Models VSUTE VSUHE 20 25kW 76mm 3ins Nom Dia 35...
Page 36: ...Figure 43 Vision Heater Assembly Models VSUTE VSUHE 30 35kW 100mm 4ins Nom Dia 36...
Page 37: ...Figure 44 Vision Heater Assembly Models VSUTE VSUHE 40kW 100mm 4ins Nom Dia 37...
Page 38: ...Figure 45 Vision Heater Assembly Models VSUTE VSUHE 45 50kW 100mm 4ins Nom Dia 38...
Page 39: ...A Figure 46 Vision Heater Assembly Models VSLIE VSLHE VSDLE 15 25kW 8m 76mm 3ins Nom Dia 39...
Page 40: ...A Figure 47 Vision Heater Assembly Models VSLIE VSLHE VSDLE 20 25kW 10 5m 76mm 3ins Nom Dia 40...
Page 41: ...Figure 48 Vision Heater Assembly Models VSLIE VSLHE VSDLE 30 35kW 10 5m 100mm 4ins Nom Dia 41...
Page 43: ...Figure 50 Vision Heater Assy Models VSLIE VSLHE VSDLE 35 40 45 50 kW 16m 100mm 4ins Nom Dia 43...
Page 59: ...Notes 59...