OPERATING INSTRUCTIONS MANUAL

FLE-150

INDUSTRIAL / COMMERCIAL ELECTRIC HEATER

(OPERATOR MUST RETAIN FOR FUTURE REFERENCE)

Suitable for indoor or outdoor installation / Unvented / Unattended Type

26 Benfield Drive, St.Catharines, Ontario Canada L2S 3V5  

(P) 905-685-4243 - (F) 905-685-0113

Summary of Contents for FLE-150

Page 1: ...50 INDUSTRIAL COMMERCIAL ELECTRIC HEATER OPERATOR MUST RETAIN FOR FUTURE REFERENCE Suitable for indoor or outdoor installation Unvented Unattended Type 26 Benfield Drive St Catharines Ontario Canada L2S 3V5 P 905 685 4243 F 905 685 0113 ...

Page 2: ...E OR SERVICE THIS HEATER IF YOU NEED ASSISTANCE OR HEATER INFORMATION SUCH AS AN INSTRUCTIONS MANUAL LABEL ETC CONTACT THE MANUFACTURER WARNING FIRE BURN INHALATION AND EXPLOSION HAZARD KEEP SOLID COMBUSTIBLES SUCH AS BUILDING MATERIALS PAPER OR CARDBOARD A SAFE DISTANCE AWAY FROM THE HEATER AS RECOMMENDED BY THE INSTRUCTIONS NEVER USE THE HEATER IN SPACES WHICH DO OR MAY CONTAIN VOLATILE OR AIRBO...

Page 3: ... Colour coded Cam Lock power connections for easy installation Remote thermostat option available Safety Always verify that you have proper voltage supply 480V It is important to check the wiring connections inside the heater before plugging in the Cam Locks Use a meter to measure volt supply to each cam lock Work on the internal systems should only be attempted by a certified electrician and only...

Page 4: ...sembly and ensure the motor and blade are operating properly 4 Compressed air may be used to keep components free of dust and dirt build up Pre Start Checklist 1 Heater must be level and lockable wheels must be in the lock position 2 Make sure blower switch and both heat selection switches are in the OFF positions 3 Make sure the air intake is free from any obstruction s 4 Make sure the heater oul...

Page 5: ...power supply 5 Pull Master button to the out position 6 Determine Manual or Remote Thermostat if remote set desired temperature 7 Turn Blower on off switch to the ON position The blower will start and the green air flow light will come on 8 Turn on heater settings as desired 150kW 60kW 90kW combined Failure to have proper air flow will cause unit to overheat and shut down The green light should co...

Page 6: ...0 5300 138F 79 DB 90 kW 307 000 4650 101F 76 DB 60kW 205 000 4100 67F 73 DB FAN ONLY 6800 N A 85 DB SHUTDOWN 1 Move all heat control setting to the OFF position 2 Leave Fan in the ON position for 3 5 minutes 3 Turn Fan OFF blower is preset to run for 30 seconds before coming to a complete stop 4 Push Master button IN 5 Shut off all power source 6 Disconnect all power sources 7 Store heater ...

Page 7: ...T KW 512 000 btu BLOWER 7 1 2 H P TEMPERATURE RISE above ambient 60KW 67 F 90KW 101 F 150 KW 138 F AMP DRAW MOTOR 7 AMPS 60KW 64 AMPS 90KW 97 AMPS 150KW 161 AMPS DB noise level FAN ONLY 85 60KW 73 90KW 76 150KW 79 INLET SIZE 16 Dia OUTLET SIZE 20 Dia Designed for 20 Dia Ducting DIMENSIONS 40 X 58 X 33 H X L X W IN WEIGHT 560 LBS AIR CIRCULATION 6800 CFM ...

Page 8: ...5 HP MOTOR FLE 1503 480 VOLT FLE 1503A 575VOLT FLE 1504 480 VOLT FLE 1504A 575 VOLT FUSES FLE 1509 125 Amp Class T FLE 1510 90 Amp Class T FLE 1511 10 Amp Class CC FLE 631 Amp Class CC FLE 632 5 Amp AGC Glass TRANSFORMER FLE 627 480V FLE 627A 575V CONTACTOR FLE 1507 90 amp 2 PER UNIT GROUNDING BLOCK FLE 621 RELAY FLE 626 2 PER UNIT ...

Page 9: ...2 POSITION SWITCH FLE 633 60KW 90KW THERMOSTAT MANUAL BLOWER ON OFF EMERGENCY STOP BUTTON FLE 634 GREEN AIR PROVEN LIGHT FLE 636 FLE 635 HIGH LIMIT AIR PROVEN LIGHT THERMOSTAT FV 414B N C CONTACT BLOCK FLE 639 3 PER UNIT N O CONTACT BLOCK FLE 640 7 PER UNIT FLE 1513 ...

Page 10: ... 610 6 RIGID FLE 611 BLUE FLE 612 BLACK FLE 613 GREEN FLE 614 RED CAM LOCK PANEL CAM LOCK DETACHABLE FLE 615 BLUE FLE 616 BLACK FLE 617 GREEN FLE 618 RED SNAP COVERS PANEL FLE 611A BLUE FLE 612A BLACK FLE 613A GREEN FLE 614A RED INLET GUARD FLE 1514 ...

Page 11: ...IPTION FLE 150FR OUTER FRAME FLE 157 RIGHT SIDE PANEL FLE 158 LEFT SIDE PANEL FLE 159 REAR PANEL FLE 160 FRONT PANEL FLE 162 TOP PANEL FLE 162B TOP PANEL ACCESS DOOR FLE 170 CONTROL PANEL RAIN GUARD BODY PANELS ...

Page 12: ...THREE PER HEATER FLE 1512 AIR PROVING SWITCH COMPLETE FLE 1513 OUTLET HIGH LIMIT 250 F FLE 1514 INLET GUARD FLE 609 6 LOCKABLE SWIVEL CASTER FLE 610 6 RIGID CASTER FLE 611 BLUE MALE PANEL CAM LOCK FLE 611A BLUE SNAP COVER FLE 612 BLACK MALE PANEL CAM LOCK FLE 612A BLACK SNAP COVER FLE 613 GREEN MALE PANEL CAM LOCK FLE 613A GREEN SNAP COVER FLE 614 RED MALE PANEL CAM LOCK FLE 614A RED SNAP COVER FL...

Page 13: ...ITION SWITCH FLE 634 EMERGENCY STOP BUTTON FLE 635 RED HIGH LIMIT NON PROVEN AIR LIGHT TWO PER HEATER FLE 636 GREEN AIR PROVEN LIGHT FLE 637 BULBS FOR FLE 635 FLE 636 FLE 638 OPERATOR BLOCK FOR FLE 635 FLE 636 FLE 639 N C CONTACT BLOCK THREE PER HEATER FLE 640 N O CONTACT BLOCK SEVEN PER HEATER ...

Page 14: ...aker FUSES Blower runs no heat kW setting is in the off position s Move kW swtich to apppropiate kW setting Thermostat option not selected properly Check thermostat setting position If in the remote position thermostat may not Check thermostat plug to make sure it is be plugged in properly Plugged in securely Remote thermostat set too low Adjust thermostat control Sail switch out of adjustment or ...

Page 15: ......