9-2
INTERBUS Master Connection
RECO PLC ISP200-R/G2
DOK-CONTRL-MTS-R0*.2G2-PR01-EN-P
The P.C.B. LK IBM 2 possesses the following features:
INTERBUS protocol (DIN E 19 258),
up to 256 bus segments,
up to 16 user levels,
up to 512 users per configuration,
up to 4096 inputs and 4096 outputs per configuration (512 bytes),
up to 32 INTERBUS loop users per bus segment,
CMD G4 support.
The configuration and commissioning of the INTERBUS occurs by the
INTERBUS configurator IBS CMD G4 (see DOK-CONTRL-IBS*CMD****-
AW...) and the I/O editor of the WinPCL programming interface (see
DOK-CONTRL-WINPCL*4VRS-AW...). For the configuration the interface
cable IKB0030 is required.
9.2
Setting of the I/O Address
The setting of the DIP switch S1 must be as follows (default setting), so
that the P.C.B. IBM 2 can be addressed via the PC/104 bus:
1
2
3
4
5
6
7
8
Address
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
120
h
Fig. 9-2: Setting of DIP switch S1
9.3 Technical
Data
Supply
Operation voltage:
+5 VDC, 5 % / 400 mA
Interface data
Communication interface:
2-line remote bus, RS422,
without electrical isolation
Diagnostic interface:
RS232C
Operation conditions
Operation temperature:
0 °C - + 55 °C
Storage temperature:
-25 °C - +70 °C
Relative humidity:
Max. 75 %, condensation to be avoided
Fig. 9-3:
Technical data
Summary of Contents for DURADRIVE SYSTEM200
Page 1: ...Project Planning Manual DOK CONTRL MTS R0 2G2 PR01 EN P SYSTEM200 RECO PLC ISP200 R G2 ...
Page 6: ...IV Contents RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 26: ...4 6 Technical Data RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 30: ...5 4 Communication RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 42: ...6 12 Startup RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 46: ...7 4 RECO PLC MTS R01 2 RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 50: ...8 4 RECO PLC MTS R02 2 RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 54: ...9 4 INTERBUS Master Connection RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 66: ...12 4 Serial Interfaces RECO PLC ISP200 R G2 DOK CONTRL MTS R0 2G2 PR01 EN P ...
Page 85: ......