ERV
98
BMS ACCESS
Next, set the BACnet Device ID. This screen allows you to set the ID digit by digit.
12.3.3 BACnet MSTP Settings
First, set the BACnet Device ID. This screen allows you to set the ID digit by digit.
NOTE: Whenever
the BMS type is
changed, power to
the controller must
be cycled.
Next, set the BACnet MSTP Address, Baud rate, Max Master and Max Info frames as needed.
If you need to set the timing values, you can do that here.
12.3.4 BACnet MSTP Wiring
The BACnet MSTP network is wired into the four-pin connector named J3 Disp. In the upper
left-hand corner of the controller. This is also used for a RUT display so the two cannot be
used at the same time. For MSTP, use the plus (+) and minus (-), as well as the GND for
reference if desired.
DO NOT
use the +Vterm terminal. If you happen to plus a three-pin block in here and use the
wrong three pins you might damage the port.