21
1.800.627.4499
Premium Commercial Controls
ERV
UNIT CONFIGURATION
4.0 UNIT CONFIGURATION
4.1 CONFIGURE GENERAL SETTING
There are several general settings that are need for correct operation of the controller.
4.1.1 Setting the Time and Date
It is important to have the correct time and date for alarm time stamps and logging.
u
Set Refresh to YES, It will turn back to NO after changing the display to the current controller
time and date.
u
Change the Time ad Date accordingly. (Day is automatically generated.)
4.1.2 Setting the Unit of Measure
The controller supports the following settings:
u
SI (bar, Celsius)
u
USA (psi, Fahrenheit)
u
UK (bar, Celsius)
u
CAN (psi, Celsius)
Set the Unit of Measure to the desired units for the display.
4.1.3 Setting the IP Address of the Controller
The controller IP address may be used for the BMS, networking, or local access.
u
Set the DHCP to OFF if using a static IP
u
Set the IP address and Mask
u
Set Update to YES
u
Cycle power to the controller