CAREL
Modbus
ON
OFF
Address
Ext.
Prot
Baud
Address
Ext Baud Prot
EXPANSION MODULE
X3-25
X3-27
DUCT PRESSURE SENSOR
P/N 131315
X3-21
4.2.6 CA Temperature Sensor
The CA Temperature sensor is automatically enabled if the heating and/or cooling is enabled. If
it is not connected, an alarm will occur. If your unit was ordered with heating and/or cooling, the
supply temperature sensor should be included but may need to be installed down the duct to
prevent cycling of heating or cooling. The sensor uses a special curve and cannot be swapped
with standard T2 or T3 NTC sensors.
UNIT CONFIGURATION
NOTE: When wiring
sensor, do not wire
directly to the
expansion module;
wire to the X3 terminal
block, see Figure 4.2.0.
CA TEMPERATURE SENSOR
P/N 131318
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
with offset
no offset
19.2 K
9.6 K
38.4 K
57.6 K
CAREL
Modbus
ON
OFF
Address
Ext.
Prot
Baud
Address
Ext Baud Prot
EXPANSION MODULE
X3-27
X3-26
NOTE: When wiring
sensor, do not wire
directly to the
expansion module;
wire to the X3 terminal
block, see Figure 4.2.0.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
with offset
no offset
19.2 K
9.6 K
38.4 K
57.6 K
CAREL
Modbus
ON
OFF
Address
Ext.
Prot
Baud
Address
Ext Baud Prot
EXPANSION MODULE
X3-24
X3-27
SPACE PRESSURE SENSOR
P/N 131314
X3-21