1.800.627.4499
Premium Commercial Controls
ERV
100
SYSTEM MONITORING
TYPE
INSTANCE
VARIABLE NAME
DESCRIPTION
VALUE
RANGE
READ/WRITE
(RET)
Analog Value
42
SF_VOCSetP.Val
SF VOC Setpoint
PPM
Read_Writeable (X)
Analog Value
43
EF_ConstSpeedSetP.Val EF Constant Speed
Setpoint
%
Read_Writeable (X)
Analog Value
44
EF_FlowControlSetP.Val EF Flow Control Setpoint
CFM
Read_Writeable (X)
Analog Value
45
EF_SF_TrackingSetP.Val EF SF Tracking Setpoint
%
Read_Writeable (X)
Analog Value
46
EF_ReturnStaticSetP.
Val
EF Return Static Setpoint iwc
Read_Writeable (X)
Analog Value
47
CoolLockoutTemp
OA Cooling Lockout
Temperature
F
Read_Writeable (X)
Analog Value
48
HeatLockoutTemp
OA Heating Lockout
Temperature
F
Read_Writeable (X)
Analog Value
50
Econ_Temp_Diff
Economizer Temperature
Differential
F
Read_Writeable (X)
Analog Value
51
Economizer.Econ_Low_
OA_Temp_Limit
Economizer Low OA
Temp Limit
F
Read_Writeable (X)
Analog Value
52
Economizer.Econ_
Hysteresis
Economizer Hysteresis
Btu/lb
Read_Writeable (X)
Analog Value
53
BMS_CO2_Reading
BMS CO2 Reading (in lieu
of attached sensor)
PPM
Read_Writeable
Analog Value
54
BMS_Space_Press_
Reading
Coil LAT Setpoint for
dehumidification
F
Read_Writeable (X)
Analog Value
55
Occ_HTG_Setp.Val
Occupied Heating
Setpoint
F
Read_Writeable (X)
Analog Value
56
Occ_CLG_Setp.Val
Occupied Cooling
Setpoint
F
Read_Writeable (X)
Analog Value
58
Economizer.Econ_Low_
RA_Temp_Limit
Economizer.Econ_Low_
RA_Temp_Limit
F
Read_Writeable (X)
Analog Value
59
SF_CO2FlowMinCO2.
Val
SF Flow: MinCO2
PPM
Read_Writeable (X)
Analog Value
60
SF_CO2FlowMaxCO2.
Val
SF Flow: Max CO2
PPM
Read_Writeable (X)
Analog Value
61
SF_CO2FlowMinFlow.
Val
SF Flow: Min Flow
CFM
Read_Writeable (X)
Analog Value
62
SF_CO2FlowMaxFlow.
Val
SF Flow: Max Flow
CFM
Read_Writeable (X)
Analog Value
77
Defrost_OA_SetP.Val
Frost control OA Setpoint
Low Limit
F
Read_Writeable (X)
Analog Value
78
Defrost_EA_Low_SetP.
Val
Frost control EA Setpoint
Low Limit
F
Read_Writeable (X)
Analog Value
79
Defrost_EA_High_SetP.
Val
Frost control EA High
Limit Setpoint
F
Read_Writeable (X)
Binary Input
8
OA_Damp.Val
OA Damper Command
Closed/
Open
Read_NoWrite
Binary Input
9
RA_Damp.Val
RA Damper Command
Closed/
Open
Read_NoWrite
Binary Input
13
Tempering_Mode.Val
Tempering Mode
Heat/Cool Read_NoWrite
Binary Input
14
AlarmMng.AlrmRes
Alarm Reset Status
No/Yes
Read_NoWrite