1.800.627.4499
Premium Commercial Controls
ERV
146
15.6.2.3 Motor Specific VFD Parameter Settings
PARAMETER #
P108
P165
LENZE AC
TECH VFD PN
3PH MOTOR
PN
MOTOR
BRAND
HP
FLA
VFD OUTPUT
AMPS
MOTOR
OVERLOAD
VOLTAGE
136506 wired
1PH
136297_001
Marathon
2
6.0
7.0
86
208
136506 wired
3PH
136297_001
Marathon
2
6.0
7.0
86
208
136508
136298_001
Marathon
2
2.9
3.5
83
460
136509
136299_001
Marathon
2
2.3
2.7
85
575
136511
136295_000
Marathon
5
15
16.5
91
208
136512
136295_000
Marathon
5
7.0
8.2
85
460
136513
136296_000
Marathon
5
5.6
6.1
90
575
136509
136356_000
106356_000
Baldor
1.5
1.8
2.7
67
575
136509
136356_001
WEG-S
1.5
1.62
2.7
60
575
136509
136357_000
106357_000
Baldor
2
2.3
2.7
85
575
136509
136357_001
WEG-S
2
2.18
2.7
81
575
136465
136314_001
106314_000
Baldor
3
3.3
3.9
85
575
136465
136314_002
WEG-S
3
3.05
3.9
78
575
136513
136315_001
106315_000
Baldor
5
5.3
6.1
87
575
136513
136315_002
WEG-S
5
5.19
6.1
85
575
136466
136360_000
106360_000
Baldor
7.5
7.6
9
85
575
136466
136360_001
WEG-S
7.5
7.26
9
81
575
136467
136361_000
106361_000
Baldor
10
9.6
11
88
575
136467
136361_001
WEG-S
10
9.76
11
89
575
136467**
106315_000
Baldor
5 x 2
10.6
11
96
575
REFERENCE