![REMKO Smart Com Instructions For Use Manual Download Page 9](http://html1.mh-extra.com/html/remko/smart-com/smart-com_instructions-for-use-manual_1438876009.webp)
WKF/HTS/WSP IP interface functional diagram
L N
A
B
C
D
E
F
2
1
4
3
5
6
6
5
a
b
Fig. 4: Functional diagram for an IP interface
a
WKF/HTS/WSP indoor unit
b: parts to be provided by the customer
A: KNX power supply (provided by the customer)
B: KNXnet/IP interface (2 x RJ45, factory fitted)
IP: 10.210.210.* (DHCP)
C: Ethernet router (building network, optional)
D: REMKO SMT controller (heat pump)
IP: 10.210.210.2 (fixed)
E: Touch display (heat pump)
IP: 10.210.210.1 (fixed)
F: USB/Ethernet adapter (optional)
1: Mains voltage (230V)
2: Auxiliary voltage (24V DC)
3: Bus voltage (29V throttled)
4: KNX-BUS
5: min. CAT 5 e
6: Twisted Pair