REMKO Smart Com Instructions For Use Manual Download Page 5

n

Spaces in which refrigerant can leak sufficient

to load and vent. Otherwise there is danger of

suffocation.

n

All housing parts and device openings, e.g. air

inlets and outlets, must be free from foreign

objects, fluids or gases.

n

The units must be inspected by a service tech-

nician at least once annually. Visual inspec-

tions and cleaning may be performed by the

operator when the units are disconnected from

the mains.

1.6  Safety notes for installation,

maintenance and inspection

n

Appropriate hazard prevention measures must

be taken to prevent risks to people when per-

forming installation, repair, maintenance or

cleaning work on the units.

n

The setup, connection and operation of the

units and its components must be undertaken

in accordance with the usage and operating

conditions stipulated in this manual and comply

with all applicable regional regulations.

n

Local regulations and laws such as Water

Ecology Act must be observed.

n

The power supply should be adapted to the

requirements of the units.

n

Units may only be mounted at the points pro-

vided for this purpose at the factory. The units

may only be secured or mounted on stable

structures, walls or floors.

n

Mobile units must be set up securely on suit-

able surfaces and in an upright position. Sta-

tionary units must be permanently installed for

operation.

n

The units and components should not be oper-

ated in areas where there is a heightened risk

of damage. Observe the minimum clearances.

n

The units and components must be kept at an

adequate distance from flammable, explosive,

combustible, abrasive and dirty areas or

atmospheres.

n

Safety devices must not be altered or

bypassed.

1.7  Dangers of failure to observe

the safety notes

Failure to observe the safety notes may pose a risk

to people, the environment and the units. Failure to

observe the safety notes may void any claims for

damages.

In particular, failure to observe the safety notes

may pose the following risks:

n

The failure of important unit functions.

n

The failure of prescribed methods of mainte-

nance and repair.

n

Danger to people on account of electrical and

mechanical effects.

1.8  Unauthorised modification

and changes

Modifications or changes to units and components

are not permitted and may cause malfunctions.

Safety devices may not be modified or bypassed.

Original replacement parts and accessories

authorised by the manufactured ensure safety. The

use of other parts may invalidate liability for

resulting consequences.

1.9  Intended use

The Smart Com function is to connect the Remko

Smart Control controller to a factory fitted interface.

Any different or additional use is a non-intended

use. The manufacturer/supplier assumes no lia-

bility for damages arising from non-intended use.

The user bears the sole risk in such cases.

Intended use also includes working in accordance

with the operating and installation instructions and

complying with the maintenance requirements.

The threshold values specified in the technical

data must not be exceeded.

1.10  Warranty

For warranty claims to be considered, it is essential

that the ordering party or its representative com-

plete and return the "certificate of warranty" to

REMKO GmbH & Co. KG at the time when the

units are purchased and commissioned.

The warranty conditions are detailed in the "Gen-

eral business and delivery conditions". Further-

more, only the parties to a contract can conclude

special agreements beyond these conditions. In

this case, contact your contractual partner in the

first instance.

 

 

 

 

 

5

Summary of Contents for Smart Com

Page 1: ...r use SD Read the instructions prior to performing any task REMKO Smart Com Activation of Smart Com for Smart Control Touch regulation 0239 2019 12 Edition 2 en_GB to integrate the heat pump into a Sm...

Page 2: ...d these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject to modifica...

Page 3: ...ction 5 1 7 Dangers of failure to observe the safety notes 5 1 8 Unauthorised modification and changes 5 1 9 Intended use 5 1 10 Warranty 5 1 11 Transport and packaging 6 1 12 Environmental protection...

Page 4: ...rns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This combination of symbol and signal word warns of a potentially hazardous situation which i...

Page 5: ...ed 1 7 Dangers of failure to observe the safety notes Failure to observe the safety notes may pose a risk to people the environment and the units Failure to observe the safety notes may void any claim...

Page 6: ...ronmentally safe manner e g using certified firms and recy cling specialists or at collection points 2 System requirements Note the following Programming can only be carried out via a KNX system integ...

Page 7: ...rry out the work described below without the KNX module being supplied with power the heat pump cannot be commissioned Connect the terminals 3 4 of the already installed KNX module with the on site po...

Page 8: ...2 1 4 3 Fig 2 HTS WSP wiring diagram 1 Touch display 2 I O module 3 KNX BUS 4 24V DC 2 1 4 3 Fig 3 WKF wiring diagram 1 Touch display 2 I O module 3 KNX BUS 4 24V DC REMKO Smart Com 8...

Page 9: ...ower supply provided by the customer B KNXnet IP interface 2 x RJ45 factory fitted IP 10 210 210 DHCP C Ethernet router building network optional D REMKO SMT controller heat pump IP 10 210 210 2 fixed...

Page 10: ...y provided by the customer B KNXnet IP interface 2 x RJ45 factory fitted IP 10 210 210 DHCP C Ethernet router building network optional D REMKO SMT controller heat pump IP 10 210 210 2 fixed E Touch d...

Page 11: ...ected to the bus line These addresses are not used when assigning the addresses NOTICE If additional bus devices are added at a later time one or several of the physical addresses could be assigned mo...

Page 12: ...talling the Smart Com function on the REMKO Smart Control con troller NOTICE Before removing and inserting the SD card the system must be powered down 1 After you have powered down the system remove t...

Page 13: ...tion is complete 6 Configuring the Smart Com function The settings for the Smart Com function can be made in the Expert level To do so touch the REMKO logo in the upper right corner of the dis play Us...

Page 14: ...cal address for the SMT controller must be located topologically in line with the KNX interface i e if the KNX interface has address 1 1 1 the con troller must receive address 1 1 2 or 1 1 3 for examp...

Page 15: ...C CRWT 0 15 0 7 0 255 CRT 5 0 8 HW set temperature C CRWT 0 15 0 7 0 255 CW 5 0 9 HW actual temperature C CRWT 0 15 0 7 0 255 CRT 5 0 10 One off hot water C CRWT 0 15 0 7 0 255 CW 5 0 11 Alarm signal...

Page 16: ...0 31 Unmix HC room target temp C CRWT 0 15 0 7 0 255 CW 5 0 32 1st mixed HC room target temp C CRWT 0 15 0 7 0 255 CW 5 0 33 2nd mixed HC room target temp C CRWT 0 15 0 7 0 255 CW 5 0 34 3rd mixed HC...

Page 17: ...0 255 CRT 5 0 48 Cooling circuit operating mode C CRWT 0 15 0 7 0 255 CRT 5 0 49 Heat pump energy C CRWT 0 15 0 7 0 255 CRT 5 0 50 Heating energy C CRWT 0 15 0 7 0 255 CRT 5 0 51 Hot water energy C C...

Page 18: ...rrent room climate mode for the SMT controller is also on cooling including cooling in auto matic mode 3 5 0 4 SMT Operating mode Switching DPT 20 102 DPT_HVAC Mode 0 Auto 1 Comfort 2 Standby 3 Night...

Page 19: ...defrosting active 8 5 0 9 HW target temperature DPT 9 001 DPT_Value_Te mp 273 C 670 760 C 2 byte C W The HW target temperature is transferred from the KNX bus to the Smart Control controller 9 5 0 10...

Page 20: ...C 2 byte C R T The Smart Control con troller transfers the hot water temperature average of the inlet tem perature and the return temperature to the KNX bus 17 5 0 18 Unmix HC room temper DPT 9 001 DP...

Page 21: ...s 23 5 0 24 Unmix HC room humidity DPT 9 007 DPT_Value_H umidity 0 100 2 byte C W The room temperature is sent from the KNX bus to the Smart Control controller and used for the circuit s room temperat...

Page 22: ...r DPT 9 001 DPT_Value_Te mp 273 C 670 760 C 2 byte C W A room temperature target value is transferred from the KNX bus e g from a KNX room temperature controller to the Smart Control controller and co...

Page 23: ...presence object DPT 1 018 DPT_Occu pancy 0 Not present 1 Present 1 bit C W A presence object is trans ferred from the KNX bus e g from a KNX room temperature controller to the Smart Control con troll...

Page 24: ...oper ating mode HVACMode to the KNX bus when changed e g depending on the presence object time programme and room climate mode 45 5 0 46 2nd mixed HC operating mode DPT 20 102 DPT_HVAC Mode 0 Auto 1...

Page 25: ...g depending on the presence object time programme and room climate mode 49 5 0 50 Heat pump energy DPT 13 013 DPT_ActiveE nergy_kWh 2147483648 kWh 2147483647 kWh 4 byte C R T The Smart Control con tro...

Page 26: ...eating mode active 8 LED for cooling mode active 9 LED for anti freeze protection mode 10 LED for dew point mode non functional The address in the relevant heating circuit e g unmixed heating circuit...

Page 27: ...ding on the presence object 33 5 0 38 Unmix HC presence object DPT 1 018 DPT_Occu pancy 0 Not present 1 Present 1 bit K S T The room temperature con troller transfers the presence object alternating e...

Page 28: ...ard for the I O module is black The SD card for the regula tion of the heat pump as well as for the con nected remote controls have a white side NOTICE The SD cards must not be mixed up 3 After replac...

Page 29: ...se it is not necessary to alter any other set tings Commissioning Restore counter readings Confirm Yes adopt previously set counter values User settings By confirming the user settings with Yes all of...

Page 30: ...ling the Smart Com 12 Intended use 5 R Room temperature controller 26 S Safety Dangers of failure to observe the safety notes 5 General 4 Identification of notes 4 Notes for inspection 5 Notes for ins...

Page 31: ......

Page 32: ...5232 606 260 E mail info remko de URL www remko de REMKO GmbH Co KG Klima und W rmetechnik Im Seelenkamp 12 32791 Lage Hotline within Germany 49 0 5232 606 0 Hotline International 49 0 5232 606 130 W...

Reviews: