CO
1)
Grp.-
addr.
2)
Name
3)
DPT
4)
Size
5)
Communica-
tion flag
6)
Function description
13
5/0/14
1st mixed HC
actual temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the hot
water temperature
(average of the inlet tem-
perature and the return
temperature) to the KNX
bus.
14
5/0/15
2nd mixed HC
actual temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the hot
water temperature
(average of the inlet tem-
perature and the return
temperature) to the KNX
bus.
15
5/0/16
3rd mixed HC
actual temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the hot
water temperature
(average of the inlet tem-
perature and the return
temperature) to the KNX
bus.
16
5/0/17
4th mixed HC
actual temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
R
-
T
The Smart Control con-
troller transfers the hot
water temperature
(average of the inlet tem-
perature and the return
temperature) to the KNX
bus.
17
5/0/18
Unmix. HC
room temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
18
5/0/19
1st mixed HC
room temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
19
5/0/20
2nd mixed HC
room temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
REMKO Smart Com