CO
1)
Grp.-
addr.
2)
Name
3)
DPT
4)
Size
5)
Communica-
tion flag
6)
Function description
47
5/0/48
4th mixed HC
operating mode
DPT 20.102
(DPT_HVAC-
Mode)
(0) Auto
(1) Comfort
(2) Standby
(3) Night (Eco)
(4) Protection
mode (frost/
heat)
1 byte
C
R
-
T
The Smart Control con-
troller transfers the oper-
ating mode (HVACMode) to
the KNX bus when
changed (e.g. depending
on the presence object,
time programme and room
climate mode).
48
5/0/49
Cooling circuit
operating mode
DPT 20.102
(DPT_HVAC-
Mode)
(0) Auto
(1) Comfort
(2) Standby
(3) Night (Eco)
(4) Protection
mode (frost/
heat)
1 byte
C
R
-
T
The Smart Control con-
troller transfers the oper-
ating mode (HVACMode) to
the KNX bus when
changed (e.g. depending
on the presence object,
time programme and room
climate mode).
49
5/0/50
Heat pump
energy
DPT 13.013
(DPT_ActiveE-
nergy_kWh)
-2147483648
kWh -
2147483647
kWh
4 byte
C
R
-
T
The Smart Control con-
troller transfers the counted
energy quantities to the
KNX bus.
50
5/0/51
Heating energy
DPT 13.013
(DPT_ActiveE-
nergy_kWh)
-2147483648
kWh -
2147483647
kWh
4 byte
C
R
-
T
The Smart Control con-
troller transfers the counted
energy quantities to the
KNX bus.
51
5/0/52
Hot water
energy
DPT 13.013
(DPT_ActiveE-
nergy_kWh)
-2147483648
kWh -
2147483647
kWh
4 byte
C
R
-
T
The Smart Control con-
troller transfers the counted
energy quantities to the
KNX bus.
1)
Communication object (CO) number
2)
Factory setting for group addresses (GA) /
3)
Data point designation
4)
Data point type (DPT) /
5)
Data point size
6)
Communication/ flags: C = Communication, R = Read, W = Write, T = Transfer
25