CO
1)
Grp.-
addr.
2)
Name
3)
DPT
4)
Size
5)
Communica-
tion flag
6)
Function description
27
5/0/28
4th mixed HC
room humidity
DPT 9.007
(DPT_Value_H
umidity)
0 % - 100 %
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
28
5/0/29
Cooling circuit
room humidity
DPT 9.007
(DPT_Value_H
umidity)
0 % - 100 %
2 byte
C
-
W
-
The room temperature is
sent from the KNX bus to
the Smart Control controller
and used for the circuit's
room temperature influ-
ence. The selection param-
eter for the room control
must be set to KNX for this.
29
5/0/30
Time
DPT 10.001
(DPT_Time-
OfDay)
3 byte
C
R
-
T
The Smart Control con-
troller sends the controller's
time to the KNX bus.
30
5/0/31
Date
DPT 11.001
(DPT_Date)
3 byte
C
R
-
T
The Smart Control con-
troller sends the controller's
date to the KNX bus.
31
5/0/32
Unmix. HC
room target
temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
A room temperature target
value is transferred from
the KNX bus (e.g. from a
KNX room temperature
controller) to the Smart
Control controller and con-
verted into an offset (KNX
target value adjustment).
32
5/0/33
1st mixed HC
room target
temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
A room temperature target
value is transferred from
the KNX bus (e.g. from a
KNX room temperature
controller) to the Smart
Control controller and con-
verted into an offset (KNX
target value adjustment).
33
5/0/34
2nd mixed HC
room target
temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
A room temperature target
value is transferred from
the KNX bus (e.g. from a
KNX room temperature
controller) to the Smart
Control controller and con-
verted into an offset (KNX
target value adjustment).
34
5/0/35
3rd mixed HC
room target
temper.
DPT 9.001
(DPT_Value_Te
mp)
-273°C - 670
760°C
2 byte
C
-
W
-
A room temperature target
value is transferred from
the KNX bus (e.g. from a
KNX room temperature
controller) to the Smart
Control controller and con-
verted into an offset (KNX
target value adjustment).
REMKO Smart Com
22