![REMKO Smart Com Instructions For Use Manual Download Page 18](http://html1.mh-extra.com/html/remko/smart-com/smart-com_instructions-for-use-manual_1438876018.webp)
7
Data points
Data points
CO
1)
Grp.-
addr.
2)
Name
3)
DPT
4)
Size
5)
Communica-
tion flag
6)
Function description
0
5/0/1
On/off
(Switching)
DPT 1.001
(DPT_Switch)
(0) Off
(1) On
1 bit
C
-
W
-
(0) Off: Switches room cli-
mate mode to standby
(1) On: Switches room cli-
mate mode to the operating
mode selected (by object
2) (i.e. to heating or
cooling)
1
5/0/2
Heating/
cooling
(Switching)
DPT 1.100
(DPT_Heat-
Cool)
(0) Cooling
(1) Heating
1 bit
C
-
W
-
(0) Cooling: Switches room
climate mode to cooling
(1) Heating: Switches room
climate mode to heating
2
5/0/3
Heating/
cooling
(Status)
DPT 1.100
(DPT_Heat-
Cool)
(0) Cooling
(1) Heating
1 bit
C
R
-
T
Returns the value 0
(cooling) if the current room
climate mode for the SMT
controller is also on cooling
(including cooling in auto-
matic mode)
3
5/0/4
SMT
Operating
mode
(Switching)
DPT 20.102
(DPT_HVAC-
Mode)
(0) Auto
(1) Comfort
(2) Standby
(3) Night (Eco)
(4) Protection
mode (frost/
heat)
1 byte
C
-
W
-
(0) Auto: The SMT con-
troller and all room control-
lers work in auto mode.
(1) Comfort: The SMT con-
troller works in comfort
mode. The room controllers
work in auto mode.
(2) Standby: The SMT con-
troller and all room control-
lers work in standby mode.
(3) Night (Eco): The SMT
controller and all room con-
trollers work in eco mode.
4
5/0/5
SMT
Operating
mode
(Status)
DPT 20.102
(DPT_HVAC-
Mode)
(0) Auto
(1) Comfort
(2) Standby
(3) Night (Eco)
(4) Protection
mode (frost/
heat)
1 byte
C
R
-
T
The Smart Control con-
troller transfers the oper-
ating mode (HVACMode)
from object 3 when the
KNX bus is changed.