Regency
®
PG36 Gas Fireplace
|
9
installation
Note: 1029mm is the minimum height for
both flex termination or Simpson
Dura-Vent flueing.
Mantel Leg Clearances
Combustible mantel leg clearances as per diagram
below:
Maximum 38mm projection at 51mm minimum
clearance.
the unit. Total facing thickness can vary from
13mm to 32mm thick.
2. Frame in the enclosure for the unit with framing
material.
Note: The unit does not have to be completely
enclosed in a chase. The clearance on
top of the unit is 0mm to the standoffs so
combustible building materials can be laid
directly on top of the standoffs. You must
maintain (38mm) clearance from the flue
to combustible materials for flex (32mm)
for Simpson Dura-Vent).
152 mm Side Walll
127mm
51mm
M
a
n
te
l
le
g
M
a
n
te
l
le
g
P 36
G
F ireplace
Allowable mantel leg
projection.
7
6
m
m
3
8
m
m
Mntle g2.e ps
Framing and Finishing
1. Determine the total thickness of facing material
(e.g. plasterboard plus ceramic tiles) to allow
the finished surface to be flush with the front of
B
Wood stud on edge
A
C
D
*
Minimum Height
to Combustible
Material
3.
Use steel studs for framing where the
38mm clearance from the flue to combustible
material cannot be maintained, e.g. front top
header.
324mm
89mm 102mm
51mm
1029mm
914m
m
826m
m
254mm dia. hole
through wall for Flex
or for DuraVent
Top Header
Opening for gas
connection
13mm
Plasterboard
Install Side Nailing Strips, Top Facing
Support, and Top Standoffs before unit is
slipped into position. See "Unit Assembly
Prior to Installation" section for assembly
details.
NOTE:
When using the Premium Flush Front
option, a finishing trim (962mm cover)
needs to be installed to cover the spacers.
Maintain a physical gap between lining
and spacers 2-5mm. (5mm clearance to
framing each side).
Standard Framing Dimensions
A
B
C
D
921mm 921mm 324mm 1169mm*
Framing Dimensions with Premium
Flush Front Option
A
B
C
D
944mm 946mm 432mm 1182mm*
* 'D' is Minimum height to combustible ma-
terials including the Minimum 51mm Top
clearance to the Horizontal Flue, see flue
clearances in section "Clearances."
4. For exterior walls, insulate the enclosure to
the same degree as the rest of the house,
apply vapour barrier and plasterboard, as per
local installation codes.
(Do not insulate the
fireplace itself.)
5. The top of the unit must not be closer than
813mm to the ceiling.
Premium Flush Front Framing
Do not use combustible material as lining (eg.
timber) around the fireplace as shown in the
shaded area in the diagram below.
MINIMUM THICKNESS OF THE FINISHING
MATERIAL: 12 mm