PG36 Gas Fireplace
|
21
installation
Aeration Adjustment
The air shutter can be adjusted by moving the
adjusting wire up or down. The wire is accessed
through the bottom louvre opening. Open the air
shutter for a blue flame or close for a yellower
flame. The burner aeration is factory set but may
need adjusting due to either the local gas supply
or altitude. This adjustment is performed by the
gas fitter.
Minimum Air Shutter Opening:
8 mm
NG
Full Open Propane
CAUTION:
Carbon will be produced if air shutter
is closed too much.
Note: Any damage due to carboning
resulting from improperly setting
the aeration controls is NOT covered
under warranty.
Closed - Tall yellow
Open - Short Blue
1. Make sure the valve is in the "OFF" position.
2. Loosen the "IN" (# 3) and/or "OUT" (# 4)
pressure tap(s), turning counterclockwise with
a 1/8" wide flat screwdriver.
3. Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" (8mm) ID hose.
4. Seal and or check the pilot outlet (# 8)
5. The pressure check should be carried out with
the unit burning and the setting should be within
the limits specified on the safety label.
6. When finished reading manometer, turn off the
gas valve, disconnect the hose and tighten the
screw (clockwise) with a 1/8" flat screwdriver.
Screw should be snug, but do not over tighten.
EV1
EV2
R.Q.
ADJ.
P.OUT
MD
4
3
2
1
Pi
n
11
8
9
10
1
2
3
4
6
7
5
SIT 845 Valve Description
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection for Pressure Regulator /
Combustion Chamber Compensation
6) Pressure Regulator for Minimum and
Maximum Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet
10) Side Outlet
11) Main Gas Inlet
PG36NG-6 System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
#37( 2.65mm)
Max. Input Rating
33 MJ/h
Min. Input Rating
20 MJ/h
Supply Pressure
min.1.13 kPa
Manifold Pressure
(High)
0.9 kPa
(Low)
0.27 kPa
Electrical
: 240 V A.C. System.
Circulation Fan
: variable speed 240 CFM.
Log Set
: Ceramic fibre, 7 per set.
Flue System:
Simpson Dura-Vent Direct
Vent System or Regency
®
Direct
Vent System (Flex)
PG36LP-6 System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
#52 (1.61mm)
Max. Input Rating
31 MJ/h
Min. Input Rating
18 MJ/h
Supply Pressure
min.2.75 kPa
Manifold Pressure
(High)
2.6 kPa
(Low)
0.72 kPa
Electrical
: 240 V A.C. System.
Circulation Fan
: variable speed 240 CFM.
Log Set
: Ceramic fibre, 7 per set.
Flue System:
Simpson Dura-Vent Co Axial
Flue System
Gas Connection
The gas line should be rigid pipe. Copper may also
be used if approved by AS5601.
The gas connection at the valve is 1/2 male. For
minimum and maximum supply pressure see the
System Data Table.
Gas Pipe Pressure Testing
The appliance must be isolated from the gas supply
piping system by closing its individual manual shut-
off valve during any pressure testing of the gas
supply piping system at test pressures equal to or
less than 1/2 psig. (3.45 kPa). Disconnect piping
from valve at pressures over 3.45 kPa (14" w.c.).
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.