Regada SP 0.1 Installation, Service And Maintenance Instructions Download Page 21

SP 0.1, SPR 0.1 

 

19

 

case that the operation angle is smaller, the pointer does not operate in the whole range of the pointer label 
(the turning is proportional with the operation angle reduction).

  

 

 

 

 

 

 

   

 

 

 

          

 

3.7  Adjustment of position controller (Fig. 8) 

 

The  built-in  position  controller  REGADA  of  new  generation  is  a  user-friendly  control  system  to 

control  actuators  with  an  analogue  signal.  The  controller  takes  advantages  of  high-power  RISC 
processor MICROCHIP to perform all functions. It provides also continuous automotive diagnostics of 
the system, error messages as well as number of relay switching and number of controller's operation 
hours. Placing an analogue signal onto the input terminals of the terminal board 86/87 (GND, -) and 88 
(+) causes that the EA output is reset.  
 

Required parameters and functions can be programmed using function buttons SW1 - SW2 and 

LED diodes D3 - D4 placed directly on the controller, see Table 2. 

 

3.7.1 

Setting of controller

 

 

The controller's microprocessor unit is in the production plant programmed to parameters given 

in 

Table 2

 (Note 2). 

 

Setting of the controller is performed using buttons and LED diodes. 

 

Adjust  the  position  and  torque  switches  and  the  position  transmitter  before  adjustment  of  the 

controller. 
Laying of adjusters and signalling elements on the board of the REGADA controller is shown on Fig. 8: 

 

 

   

 

Fig. 8 

Table 2: 

D3 (yellow) diode 

number of blinking 

Adjust menu 

D4 (red) diode 

number of blinking 

Adjusted parameter 

1 blink 

0-20mA 

2 blinks 

4-20 mA (*) (**) 

1 blink 

control signal 

3 blinks 

0-10V DC 

1 blink 

EA opens receiving signal SYS 

2 blinks 

EA closes receiving signal SYS 

2 blinks 

response for signal 

SYS-TEST 

3 blinks 

EA stops receiving signal SYS (*) 

1 blink 

EA CLOSING at increasing of control 

signal 

3 blinks 

mirroring 

(ascending/descending 

characteristics) 

2 blinks 

EA OPENING at increasing of control 

signal (*) 

4 blinks 

insensitiveness of 

controller 

1 to 10 blinks 

insensitiveness of controller of 1-10%  

(3% set by the producer) (*) 

1 blink 

narrow torque 

2 blinks 

narrow position (*) 

3 blinks 

wide torque 

5 blinks 

way of regulation 

4 blinks 

wide position 

SW1 button

 

starts  an  initialisation  routine  an  allows 
listing in the adjust menus 

SW2 button

 

setting of parameters in the chosen menu 

D1 diode

 

power on indication 

D2 diode

 

motion  to  the  direction  "opening"  indication 
(green) - "closing" (red) indication 

D3 diode

 

(yellow  light)  number  of  blinking  codes 
indicates chosen adjust menu 

D4 diode

 

(red  light)  number  of  blinking  codes 
indicates 

adjusted 

parameter 

of 

the 

controller from the chosen menu 

 F3 

Summary of Contents for SP 0.1

Page 1: ...74 0803 03 Electric part turn actuators SP 0 1 SPR 0 1 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Page 2: ...Operating angle Transmitter Warranty period months Input operating signal Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance wi...

Page 3: ...1 Installation 12 2 1 1 Mechanical connection 12 2 1 2 Electric connection and checking of function 13 2 2 Dismantling 14 3 Adjusting of actuator 14 3 1 Output position changes 14 3 2 Adjustment of po...

Page 4: ...of actuator by a semiconductor components switches have to be consulted with producer 1 2 Safety instructions EA of SP and SPR types are reserved technical devices with higher rate of danger with pos...

Page 5: ...4 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specifications of the product which are stated in the Contract The supplier is not responsible...

Page 6: ...on and operation of EA is possible in any position Usual position has vertical axis position of output part above armature and with control at the top Operating angle adjusted by stop ends must be gre...

Page 7: ...of corrosive pollution AF 2 with permanent exposure of big amount of corroding or contaminated chemicals and salt fog in execution for sea environment for sewage water disposal plant and some chemical...

Page 8: ...l part Fig 1 is placed on a control board consisting of electric motor 58 with capacitor 56 a torque unit controlled with a worm axial shift a position signalling unit 54 with a position transmitter 5...

Page 9: ...40 34 7 3 0 078 0 78 46 63 0 47 500 60 50 4 7 375 0 051 0 51 30 63 0 33 500 80 66 3 54 250 0 045 0 45 25 8 63 0 27 500 120 100 2 75 375 0 04 0 4 25 63 0 27 500 SP 0 1 SPR 0 1 type number 331 160 135...

Page 10: ...ce can be single side grounded Influence of resistance on output current 0 02 100 Influence of voltage on output current 0 02 1V Temperature dependency 0 5 10 C Output signal values at limit positions...

Page 11: ...k position transmitter Statistic data using RS 232 and personal computer number of controller operation hours frequency of relay switching in direction opening frequency of relay switching in directio...

Page 12: ...tric connection according to wiring diagrams 1 9 Conservation packing transport storing and unpacking Surfaces without surface treatment are treated by conservation preparation MOGUL LV 2 3 before pac...

Page 13: ...s not protected against direct climate influence Eventual damages to surface finish remove without delay thus preventing damage by corrosion If storing takes longer than 1 year it is necessary to insp...

Page 14: ...tuators SP R 0 1 are available in the following versions a With a flange F 03 F 04 or F05 in accordance with ISO 5211 Standard b With a stand and a lever a lever and a pull rod or without any lever wi...

Page 15: ...t is necessary to lead them separately with thrust wires or it is necessary to use shielded wires 2 The EA are delivered with bushings which in case of tight putting on the leads assure protection enc...

Page 16: ...e chapter 1 2 2 Requirements for professional qualification Disconnect the electrical servo drive from electrical power network Observe safety regulations The adjustment can be performed at a mechanic...

Page 17: ...icator in the EA SPR to function as a feedback in the position controller and if needed also in the position of a remote resistant position indicator Before the resistant transmitter adjustment the po...

Page 18: ...troke stated on the actuator s nameplate At values less than 75 the value 20mA is reduced proportionally Adjustment of the EPV in Electric Actuators SPR with controllers Disconnect the circuit with re...

Page 19: ...values of output signals in case they are reset The capacitive transmitter serves as a position transmitter of electric actuators with unified output signal of 4 20 mA in electric actuators SP 0 1 or...

Page 20: ...s 81 and 82 removing the jumper Connect power supply to the terminals 1 and 61 Disconnect the control signal from the terminals 86 and 88 Put the actuator to the direction OPENING or CLOSING with the...

Page 21: ...e switches and the position transmitter before adjustment of the controller Laying of adjusters and signalling elements on the board of the REGADA controller is shown on Fig 8 Fig 8 Table 2 D3 yellow...

Page 22: ...d closing and loads the adjusted parameters into the EEPROM memory In case that during the initialisation process an error occurs e g in connection or adjustment the initialisation process will be int...

Page 23: ...and troubleshooting 4 1 Service 1 In general it is provided that service of the EA is performed by a qualified worker in accordance with requirement given in Chapter 1 2 After putting the EA into ope...

Page 24: ...tent and periodicity During inspections and maintenance is needed to tighten all screws and nuts that affect the tightness and coverage Similarly once a year should be checked and if necessary tighten...

Page 25: ...pieces for repair purposes is allowed only by professionally qualified persons trained in the production plant or by a contracted service centre 5 Spare parts Spare part list Spare part Order Nr Posit...

Page 26: ...24 SP 0 1 SPR 0 1 6 Enclosures 6 1 Wiring diagrams Wiring diagrams for EA SP 0 1...

Page 27: ...n controller with resistant feedback connection Z239a position controller with current feedback connection Z257a 3 wire version of EPV without power supply connection Z260a 3 wire version of EPV with...

Page 28: ...with a jumper the jumper is placed in the plant If the output current signal is to be used the jumper is required to be removed 2 For the EA version with supply voltage of 24 V AC an earthling cable...

Page 29: ...SP 0 1 SPR 0 1 27 6 2 Dimensional drawings...

Page 30: ...28 SP 0 1 SPR 0 1...

Page 31: ...SP 0 1 SPR 0 1 29...

Page 32: ...30 SP 0 1 SPR 0 1...

Page 33: ...SP 0 1 SPR 0 1 31...

Page 34: ...32 SP 0 1 SPR 0 1...

Page 35: ...SP 0 1 SPR 0 1 33...

Reviews: