Regada SP 0.1 Installation, Service And Maintenance Instructions Download Page 14

12 

 

 SP 0.1, SPR 0.1 

 

 

2.  Installation and dismantling of actuator 

Abide by safety measures! 

Notes: 

 

Repeatedly verify whether placing of EA correspondents to part "Operating conditions". If actual 

conditions differ from recommended, it is necessary to consult it with manufacturer.

 

Before starting of mounting the EA onto the valve: 

  Check again whether the EA was not damaged during storing. 

  Check  whether the  adjusted  operation  angle  and  connecting  dimensions  of  the  actuator (see the 

nameplate) are in compliance with the valve parameters. 

In case of inconsonance, perform adjusting according to the part Adjustment. 

 

2.1  Installation 

 

EA  is  by  the  producer  adjusted  to  parameters  according  to  the  nameplate,  with  connecting 

dimensions according to the corresponding dimensional drawing and put it to a mid-position. 

 

2.1.1 

Mechanical connection

 

 

The actuators can be installed and operated in any position. While installing leave enough space 

for dismantling of the upper cover to allow adjusting of the control parts. 

 

Before  installation  clean  the  contact  areas  of  the  actuator  and  the  valve,  coat  the  output  shaft 

and sliding areas with a grease without any acids.   

The actuators SP(R) 0.1 are available in the following versions: 

 

a) With a flange 

F 03, F 04 or F05 in accordance with ISO 5211 Standard 

 

b)  With  a  stand 

and  a  lever,  a  lever  and  a  pull-rod  or  without  any  lever  with  output  shaft  of 

square section 

 

11x11 mm or circular section 

22 mm. 

 

The flange actuators are to be connected with a valve using four bolts with a thread M5 (F03 and 

F04 flanges) or M6 (F05 flange). The screw has to be screwed into depth of 10 mm or 12 mm. 
 

The  actuators  with  a  stand  are  fixed  to  the  base  with  two  screws  with  thread  10.  The  screw 

depth in the steel base must not be less than 10 mm, in case of a base made of aluminium alloy not 
less than 16 mm.  
 

The actuators with a small lever are connected with a controlled device with a lever mechanism 

consisting of the two pull-rod TV-160 and a 1/4 " tube with 
threads on the both ends. The actuators with a large lever 
are  connected  with  a  controlled  device  with  a  lever 
mechanism  consisting  of  the  two  pull-rod  TV-160  and  a 
1/2 " tube with threads on the both ends. While mounting 
the  coarse  setting  of  the  small  lever  on  the  actuator  can 
be changed with turning of the hub on the output shaft by 
90 ° or with turning of the lever on the hub by 60 ° or with 
the  combination  of  the  two  operations  by  30  °. Setting  of 
the large lever position can be reached with turning of the 
lever on the splined shaft.  

 

   

 

 

 

 

 

 

 

 

 

 
 
 
 
 

!

Fig.2 

 

Summary of Contents for SP 0.1

Page 1: ...74 0803 03 Electric part turn actuators SP 0 1 SPR 0 1 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Page 2: ...Operating angle Transmitter Warranty period months Input operating signal Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance wi...

Page 3: ...1 Installation 12 2 1 1 Mechanical connection 12 2 1 2 Electric connection and checking of function 13 2 2 Dismantling 14 3 Adjusting of actuator 14 3 1 Output position changes 14 3 2 Adjustment of po...

Page 4: ...of actuator by a semiconductor components switches have to be consulted with producer 1 2 Safety instructions EA of SP and SPR types are reserved technical devices with higher rate of danger with pos...

Page 5: ...4 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specifications of the product which are stated in the Contract The supplier is not responsible...

Page 6: ...on and operation of EA is possible in any position Usual position has vertical axis position of output part above armature and with control at the top Operating angle adjusted by stop ends must be gre...

Page 7: ...of corrosive pollution AF 2 with permanent exposure of big amount of corroding or contaminated chemicals and salt fog in execution for sea environment for sewage water disposal plant and some chemical...

Page 8: ...l part Fig 1 is placed on a control board consisting of electric motor 58 with capacitor 56 a torque unit controlled with a worm axial shift a position signalling unit 54 with a position transmitter 5...

Page 9: ...40 34 7 3 0 078 0 78 46 63 0 47 500 60 50 4 7 375 0 051 0 51 30 63 0 33 500 80 66 3 54 250 0 045 0 45 25 8 63 0 27 500 120 100 2 75 375 0 04 0 4 25 63 0 27 500 SP 0 1 SPR 0 1 type number 331 160 135...

Page 10: ...ce can be single side grounded Influence of resistance on output current 0 02 100 Influence of voltage on output current 0 02 1V Temperature dependency 0 5 10 C Output signal values at limit positions...

Page 11: ...k position transmitter Statistic data using RS 232 and personal computer number of controller operation hours frequency of relay switching in direction opening frequency of relay switching in directio...

Page 12: ...tric connection according to wiring diagrams 1 9 Conservation packing transport storing and unpacking Surfaces without surface treatment are treated by conservation preparation MOGUL LV 2 3 before pac...

Page 13: ...s not protected against direct climate influence Eventual damages to surface finish remove without delay thus preventing damage by corrosion If storing takes longer than 1 year it is necessary to insp...

Page 14: ...tuators SP R 0 1 are available in the following versions a With a flange F 03 F 04 or F05 in accordance with ISO 5211 Standard b With a stand and a lever a lever and a pull rod or without any lever wi...

Page 15: ...t is necessary to lead them separately with thrust wires or it is necessary to use shielded wires 2 The EA are delivered with bushings which in case of tight putting on the leads assure protection enc...

Page 16: ...e chapter 1 2 2 Requirements for professional qualification Disconnect the electrical servo drive from electrical power network Observe safety regulations The adjustment can be performed at a mechanic...

Page 17: ...icator in the EA SPR to function as a feedback in the position controller and if needed also in the position of a remote resistant position indicator Before the resistant transmitter adjustment the po...

Page 18: ...troke stated on the actuator s nameplate At values less than 75 the value 20mA is reduced proportionally Adjustment of the EPV in Electric Actuators SPR with controllers Disconnect the circuit with re...

Page 19: ...values of output signals in case they are reset The capacitive transmitter serves as a position transmitter of electric actuators with unified output signal of 4 20 mA in electric actuators SP 0 1 or...

Page 20: ...s 81 and 82 removing the jumper Connect power supply to the terminals 1 and 61 Disconnect the control signal from the terminals 86 and 88 Put the actuator to the direction OPENING or CLOSING with the...

Page 21: ...e switches and the position transmitter before adjustment of the controller Laying of adjusters and signalling elements on the board of the REGADA controller is shown on Fig 8 Fig 8 Table 2 D3 yellow...

Page 22: ...d closing and loads the adjusted parameters into the EEPROM memory In case that during the initialisation process an error occurs e g in connection or adjustment the initialisation process will be int...

Page 23: ...and troubleshooting 4 1 Service 1 In general it is provided that service of the EA is performed by a qualified worker in accordance with requirement given in Chapter 1 2 After putting the EA into ope...

Page 24: ...tent and periodicity During inspections and maintenance is needed to tighten all screws and nuts that affect the tightness and coverage Similarly once a year should be checked and if necessary tighten...

Page 25: ...pieces for repair purposes is allowed only by professionally qualified persons trained in the production plant or by a contracted service centre 5 Spare parts Spare part list Spare part Order Nr Posit...

Page 26: ...24 SP 0 1 SPR 0 1 6 Enclosures 6 1 Wiring diagrams Wiring diagrams for EA SP 0 1...

Page 27: ...n controller with resistant feedback connection Z239a position controller with current feedback connection Z257a 3 wire version of EPV without power supply connection Z260a 3 wire version of EPV with...

Page 28: ...with a jumper the jumper is placed in the plant If the output current signal is to be used the jumper is required to be removed 2 For the EA version with supply voltage of 24 V AC an earthling cable...

Page 29: ...SP 0 1 SPR 0 1 27 6 2 Dimensional drawings...

Page 30: ...28 SP 0 1 SPR 0 1...

Page 31: ...SP 0 1 SPR 0 1 29...

Page 32: ...30 SP 0 1 SPR 0 1...

Page 33: ...SP 0 1 SPR 0 1 31...

Page 34: ...32 SP 0 1 SPR 0 1...

Page 35: ...SP 0 1 SPR 0 1 33...

Reviews: