Regada SP 0.1 Installation, Service And Maintenance Instructions Download Page 18

16 

 

 SP 0.1, SPR 0.1 

3.4  Adjustment of the Electronic Position Transmitter (EPV) - the Resistive 

Transmitter (Potentiometer) with the Converter PTK 1 

3.4.1 

EPV – the 2-wire version (Fig. 4)

 

 

The  position  transmitter  with  the  converter  PTK1  is  in  the  plant  adjusted  to  have  the  output 

current signal on the terminals 81-82  as follows: 

  in the position ”open“  .................... 20 mA 

  in the position ”closed“ .................. 4 mA 

 
 

If  the  transmitter  requires  a  new  adjustment  follow  these 
steps: 

  Put  the  actuator  to  the  position  ”closed“  and  switch  the 

power supply off. 

  Adjust  the  resistive  transmitter  according  to  the  previous 

chapter. The resistance is to be metered on the terminals 
X-Y (Fig. 4). The used transmitter resistance is

 100 

 

  Switch the converter

s power supply on. 

  Turn  the  adjusting  trimmer  ZERO  (Fig.  4)  to  adjust  the 

output  current  signal  rate  measured  on  the  terminals  81-
82 to  4mA. 

  Set the actuator to the position ”open“. 

  Turn  the  adjusting  trimmer  GAIN  (Fig.  4)  to  adjust  the 

output current signal rate measured on the terminals 81-82 to  20mA. 

  Check  the  output  signal  of  the  converter  in  the  both  limit  positions,  and  repeat  the  procedure  if 

needed.  

Note: 
The  output  signal  of  4-20mA  can  be  adjusted  at  the  range  from  75  up  to  100%  of  the  rated  stroke 
stated  on  the  actuator

s  nameplate.  At  values  less  than  75%  the  value    20mA  is  reduced 

proportionally. 

Adjustment of the  EPV in Electric Actuators SPR with controllers 

  Disconnect the circuit with removing a jumper on the terminals 81 and 82. 

  Disconnect the control signal from the terminals 86/87 and 88. 

  Set  the  actuator  to  the  direction  ”OPENING”  or  “CLOSING”  with  the  handwheel,  or  with 

connecting  power  to  the  terminals  1  and  20  for  the  direction  “OPENING”  or  1  and  24  for  the 
direction “CLOSING”. 

  Set the actuator to the position “CLOSING“ and switch the converter off on the terminals 1 a 61. 

  Adjust the resistive transmitter according to the previous chapter. The resistance is to be metered 

on the terminals X-Y (Fig. 4).  

  Connect power supply to the terminals 1 and 61. 

  Turn the adjusting trimmer ZERO (Fig. 4) to adjust the output current signal rate measured on the 

terminals 81-82 to  4mA. 

  Set the actuator to the position “open”. 

  Turn the adjusting trimmer GAIN (Fig. 4) to adjust the output current signal rate measured on the 

terminals 81-82 to  20mA. 

  Check  the  output  signal  of  the  converter  in  the  both  limit  positions,  and  repeat  the  procedure  if 

needed. 

 

  Having the transmitter adjusted put the jumper again on the terminals 81 and 82 in case that the 

output signal wont be used  (the circuit through the terminals 81 and 82 should be closed).

 

  Connect the control signal to the terminals 86/87 and 88. 

Fig.4 

Summary of Contents for SP 0.1

Page 1: ...74 0803 03 Electric part turn actuators SP 0 1 SPR 0 1 INSTALLATION SERVICE AND MAINTENANCE INSTRUCTIONS...

Page 2: ...Operating angle Transmitter Warranty period months Input operating signal Serial number of electric motor Serial number of transmitter Serial number of position controller Tests made in accordance wi...

Page 3: ...1 Installation 12 2 1 1 Mechanical connection 12 2 1 2 Electric connection and checking of function 13 2 2 Dismantling 14 3 Adjusting of actuator 14 3 1 Output position changes 14 3 2 Adjustment of po...

Page 4: ...of actuator by a semiconductor components switches have to be consulted with producer 1 2 Safety instructions EA of SP and SPR types are reserved technical devices with higher rate of danger with pos...

Page 5: ...4 Warranty conditions The supplier is responsible for completeness of the delivery and guarantees these specifications of the product which are stated in the Contract The supplier is not responsible...

Page 6: ...on and operation of EA is possible in any position Usual position has vertical axis position of output part above armature and with control at the top Operating angle adjusted by stop ends must be gre...

Page 7: ...of corrosive pollution AF 2 with permanent exposure of big amount of corroding or contaminated chemicals and salt fog in execution for sea environment for sewage water disposal plant and some chemical...

Page 8: ...l part Fig 1 is placed on a control board consisting of electric motor 58 with capacitor 56 a torque unit controlled with a worm axial shift a position signalling unit 54 with a position transmitter 5...

Page 9: ...40 34 7 3 0 078 0 78 46 63 0 47 500 60 50 4 7 375 0 051 0 51 30 63 0 33 500 80 66 3 54 250 0 045 0 45 25 8 63 0 27 500 120 100 2 75 375 0 04 0 4 25 63 0 27 500 SP 0 1 SPR 0 1 type number 331 160 135...

Page 10: ...ce can be single side grounded Influence of resistance on output current 0 02 100 Influence of voltage on output current 0 02 1V Temperature dependency 0 5 10 C Output signal values at limit positions...

Page 11: ...k position transmitter Statistic data using RS 232 and personal computer number of controller operation hours frequency of relay switching in direction opening frequency of relay switching in directio...

Page 12: ...tric connection according to wiring diagrams 1 9 Conservation packing transport storing and unpacking Surfaces without surface treatment are treated by conservation preparation MOGUL LV 2 3 before pac...

Page 13: ...s not protected against direct climate influence Eventual damages to surface finish remove without delay thus preventing damage by corrosion If storing takes longer than 1 year it is necessary to insp...

Page 14: ...tuators SP R 0 1 are available in the following versions a With a flange F 03 F 04 or F05 in accordance with ISO 5211 Standard b With a stand and a lever a lever and a pull rod or without any lever wi...

Page 15: ...t is necessary to lead them separately with thrust wires or it is necessary to use shielded wires 2 The EA are delivered with bushings which in case of tight putting on the leads assure protection enc...

Page 16: ...e chapter 1 2 2 Requirements for professional qualification Disconnect the electrical servo drive from electrical power network Observe safety regulations The adjustment can be performed at a mechanic...

Page 17: ...icator in the EA SPR to function as a feedback in the position controller and if needed also in the position of a remote resistant position indicator Before the resistant transmitter adjustment the po...

Page 18: ...troke stated on the actuator s nameplate At values less than 75 the value 20mA is reduced proportionally Adjustment of the EPV in Electric Actuators SPR with controllers Disconnect the circuit with re...

Page 19: ...values of output signals in case they are reset The capacitive transmitter serves as a position transmitter of electric actuators with unified output signal of 4 20 mA in electric actuators SP 0 1 or...

Page 20: ...s 81 and 82 removing the jumper Connect power supply to the terminals 1 and 61 Disconnect the control signal from the terminals 86 and 88 Put the actuator to the direction OPENING or CLOSING with the...

Page 21: ...e switches and the position transmitter before adjustment of the controller Laying of adjusters and signalling elements on the board of the REGADA controller is shown on Fig 8 Fig 8 Table 2 D3 yellow...

Page 22: ...d closing and loads the adjusted parameters into the EEPROM memory In case that during the initialisation process an error occurs e g in connection or adjustment the initialisation process will be int...

Page 23: ...and troubleshooting 4 1 Service 1 In general it is provided that service of the EA is performed by a qualified worker in accordance with requirement given in Chapter 1 2 After putting the EA into ope...

Page 24: ...tent and periodicity During inspections and maintenance is needed to tighten all screws and nuts that affect the tightness and coverage Similarly once a year should be checked and if necessary tighten...

Page 25: ...pieces for repair purposes is allowed only by professionally qualified persons trained in the production plant or by a contracted service centre 5 Spare parts Spare part list Spare part Order Nr Posit...

Page 26: ...24 SP 0 1 SPR 0 1 6 Enclosures 6 1 Wiring diagrams Wiring diagrams for EA SP 0 1...

Page 27: ...n controller with resistant feedback connection Z239a position controller with current feedback connection Z257a 3 wire version of EPV without power supply connection Z260a 3 wire version of EPV with...

Page 28: ...with a jumper the jumper is placed in the plant If the output current signal is to be used the jumper is required to be removed 2 For the EA version with supply voltage of 24 V AC an earthling cable...

Page 29: ...SP 0 1 SPR 0 1 27 6 2 Dimensional drawings...

Page 30: ...28 SP 0 1 SPR 0 1...

Page 31: ...SP 0 1 SPR 0 1 29...

Page 32: ...30 SP 0 1 SPR 0 1...

Page 33: ...SP 0 1 SPR 0 1 31...

Page 34: ...32 SP 0 1 SPR 0 1...

Page 35: ...SP 0 1 SPR 0 1 33...

Reviews: