UM-1097
Revision B
87
Appendix 1
ViewSmart 1600+ Specifications
7.9.1
DC Power Supply Requirements
Standard ViewSmart 1600+ power requirements are 10-30VDC @ 12 watts applied to terminals 1 & 3(+)
and 5 & 7(-) of TB4 on the standard I/O Board (
see section 3.0
). Optional features increase power
consumption as described below:
•
Discrete Relay Board option; add 6.5 watts per board (assumes all 16 relays are energized).
•
Programmable Relay Board option; add 6.5 watts per board (assumes all 16 relays are energized).
•
Analog Input Board option; add 1/2 watts per board plus transmitter power consumption.
•
4-20mA Output Board option; add 2.5 watts per board.
•
Bridge Sensor Input Board option; add 3 watts max per board with eight 10-0192 modules
installed (power consumption of the sensors not included).
•
Auxiliary Standard Relay Board option; add 2.5 watts.
•
Isolated Serial Expansion Board; add 1.5 watts.
•
TB4 terminals 2, 4, 6 & 8 of the standard I/O Board provide a maximum of 500mA fused output
power for powering of auxiliary external devices such as relays, lamps or transmitters. Power
consumed from these terminals should be considered when calculating system power
consumption.
7.9.1.1
150 Watt AC – 24VDC Power Supply
*110-120 VAC @3.2A max
*220-240VAC @ 1.6A max
* A slide switch on the front of the power supply selects AC input range.
The 10-0172 150 watt power supply (Figure 3-7) is for powering the ViewSmart 1600+ and up to 16
detectors.
7.9.1.2
Relays
The ViewSmart 1600+ comes standard with five Standard SPDT 5A relays, consisting of one dedicated
HORN and one dedicated FAULT relay plus 3 programmable alarm relays. Programmable relays provide
voting logic for ALARM 1, ALARM 2, and ALARM 3. Discrete relays and additional Programmable relays
are optional. All relays are rated at 5 Amp for 28 VDC and 250 ~VAC RESISTIVE loads.
IMPORTANT
: Appropriate diode (DC loads) or MOV (AC loads) snubber devices must be
installed with inductive loads to prevent RFI noise spikes. Relay wiring should be kept separate from low
level signal wiring.
!
Summary of Contents for ViewSmart 1600+
Page 77: ...UM 1097 Revision B 67 4 7 5 4 Programmable Relays Figure 47 Webpage Programmable Relays Menu...
Page 78: ...UM 1097 Revision B 68 4 7 5 5 System Configuration Figure 48 Webpage System Configuration Menu...
Page 134: ...UM 1097 Revision B 124 Appendix 4 Menu Navigation...
Page 141: ...UM 1097 Revision B 131 Wireless Options and Accessories Expansion Options...