4.6.4.1
WaveNet Wireless
The ViewSmart 1600+ utilizes R.C. Systems’ WaveNet wireless technology to make setup simplified with
three easy steps.
1.
Power on the SenSmart 7000/7000X (for the SenSmart 7000 hold a magnet over the
Up
key, for
the SenSmart 7000X apply 10-30VDC to the power terminals).
Note
: Once the detector is on the data screen, you may notice high or low values out of the full-scale
range. These values should quickly return to the zero-gas value if no gas is present. No false alarms should
be indicated at this time as the zero-gas value will be transmitted by the detector during the user-defined
warmup delay period (up to 5 minutes).
2.
Using the magnetic interface, navigate the menus to:
a.
Ensure the Network ID matches the Network ID of the controller.
b.
Set the RTU number to the desired number.
3.
Verify proper operation by ensuring readings on gas detector and controller match.
4.6.4.2
Wireless Modbus®
Radio modules connected to the ViewSmart 1600+’s communication port may be configured through the
Radio Setup
menu. Enter the Radio Setup Menu by moving the selection bar over Radio Setup and press
Edit.
B a u d R a t e
T i me o u t ( ms )
P o l l D e l a y ( ms )
R a d i o S e t u p
F u n c t i o n
9 6 0 0
5 0 0
2 5 0
~
Mo d b u s Ma s t e r
C OM1 S e t t i n g s
COM1-4 Menus are Identical
S y s t e m I D
Mo d e
H o p C h a n n e l
10 8
S e r v e r
17
R a d i o S e t u p
Hop Channel
may be set from 1-32 using the ViewSmart 1600+ keypad and assigns the pseudo-random
radio frequency hopping pattern. A transceiver will not go
InRange
of, or communicate with, a transceiver
operating on a different
Hop Channel
.
System ID
may be set from 1-255 using the ViewSmart 1600+ keypad, and is similar to a password
character or network number and makes network eavesdropping more difficult. A transceiver will not go
in range of or communicate with a transceiver operating on a different
System ID
.
Mode
may be set for
CLIENT
or
SERVER.
For a single ViewSmart 1600+ communicating to up to 16 wireless
transceivers, Mode must = Server. If an application calls for multiple ViewSmart 1600+ locations, only one
Summary of Contents for ViewSmart 1600+
Page 77: ...UM 1097 Revision B 67 4 7 5 4 Programmable Relays Figure 47 Webpage Programmable Relays Menu...
Page 78: ...UM 1097 Revision B 68 4 7 5 5 System Configuration Figure 48 Webpage System Configuration Menu...
Page 134: ...UM 1097 Revision B 124 Appendix 4 Menu Navigation...
Page 141: ...UM 1097 Revision B 131 Wireless Options and Accessories Expansion Options...